Permit Information
Permit NumberPLM18-02703
StatusFinaled
Name WALT CULVER
Site Address 10322 W STARDUST DR
Project NameMcKay Shop
Customer Number 
ePlanReviewNo
Description
run water/sewer lines from road around main house to the shop in rear
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled3/7/20193/7/20193/7/2019PPASS
DetailsDan Ediger
Work completed by the plumbing contractor
Water and/or Sewer8/28/20188/28/20188/28/2018PPART
DetailsBill VanDegrift
sewer and water test ok ok to cover, will need to inspect the sump when they figure out what the access will be.
Water and/or Sewer8/24/20188/24/20188/28/2018PNR
DetailsBill VanDegrift
jason Phone #: ###-####
he was going to call Monday when he was ready but I never heard from him
Water and/or Sewer8/22/20188/22/20188/22/2018PNR
DetailsBill VanDegrift
Jason Phone #: ###-#### will haul in cover to get 36". need perssure test on the sewer.
Water and/or Sewer8/20/20188/21/20188/21/2018AFAIL
DetailsBill VanDegrift
Jason Phone #: ###-####
1) the cleanout on the building sewer is installed backwards
2) remove 2" and 4" ABS fittings and replace with PVC at tie in. ( can't mix materials)
3) use approved glue
4) pressure test PVC and water piping.
5) use two clamps at each joint on the water service piping
6) sleeve water at sewer crossing, 10 feet on each side of crossing.
7) provide a tapped fitting on the pressure sewer at the sump to blow out sewer.
8) provide 3' of cover on pressure sewer and water lines.
Water and/or Sewer7/17/20187/18/20187/18/2018APART
DetailsDan Ediger
Jason Phone #: ###-####.
OK to cover water with sand or chips. Pressure test before final backfill with the waste.
Use pressure pipe on the pressure sewer.
Other6/29/20186/29/20186/29/2018APASS
DetailsDan Ediger
went over the materials and fittings required to run and tie in the pressurized sewer connection.