Final | 2/7/2019 | 2/8/2019 | 2/8/2019 | A | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Rob Bristol
|
Plumbing Rough-in | 11/27/2018 | 11/27/2018 | 11/27/2018 | P | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Rob Bristol
|
Plumbing Rough-in | 11/27/2018 | 11/27/2018 | 11/27/2018 | A | NR |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Rob Bristol
|
Groundwork | 10/24/2018 | 10/24/2018 | 10/24/2018 | P | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Rob Bristol
|
Groundwork | 10/23/2018 | 10/24/2018 | 10/24/2018 | P | NR |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Rob Bristol
|