Final | 2/12/2019 | 2/12/2019 | 2/12/2019 | A | PASS |
Daryl Spivey
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Adams
|
Plumbing Rough-in | 12/9/2018 | 12/10/2018 | 12/10/2018 | A | FAIL |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Adams-Washer box water lines cannot be in a 2x4 exteriour wall. Need to add gas line to permit and test and need approved striker plate and cannot strap to vertical on 2x4 wall without protection.
|
Plumbing Rough-in | 12/4/2018 | 12/6/2018 | 12/6/2018 | P | FAIL |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Adams-Cannot run 2" kitchen sink drain into a 1 1/2" drain. Tankless water heater requires 3" clearance to combustibles from side walls and T&P requires an airgap above floor drain.
|