PLM-Aging Inspection | 6/15/2020 | 6/15/2020 | 6/15/2020 | | PASS |
Matt Wrobel
|
|
|
permit expired
|
DOC - Permit Expired | 6/15/2020 | 6/15/2020 | 6/15/2020 | P | PASS |
Matt Wrobel
|
|
|
|
PLM-Aging Inspection | 3/16/2020 | 3/16/2020 | 3/16/2020 | | PART |
Matt Wrobel
|
|
|
no calls permit will expire next aging
|
PLM-Aging Inspection | 12/16/2019 | 12/16/2019 | 12/17/2019 | | FAIL |
Matt Wrobel
|
|
|
left msg with contractor to schedule inspection
|
PLM-Aging Inspection | 9/16/2019 | 9/16/2019 | 9/16/2019 | | PART |
Matt Wrobel
|
|
|
no calls
|
Final | 1/18/2019 | 1/18/2019 | 1/18/2019 | P | NH |
Matt Wrobel
|
|
|
Please call Caleb prior to inspection so she can meet you at ###-#### Inspection requested via web by Margie Rowe
|
Final | 1/8/2019 | 1/8/2019 | 1/8/2019 | P | FAIL |
Matt Wrobel
|
|
|
Please call Kayla Hall prior to inspection ###-#### Inspection requested via web by Margie Rowe water heater vent b vent portion needs extended below drywall and drywall repaired need 1 inch shield in attic space ane 1 inch clearance from drywall penetraition t & p cannot terminate in drain pan must be run to floor existing t & p line has no approved fittings so new approved material will need to be used to run down and terminate with water alarm as t & p cannot easilly be routed to exterior
|
Final | 1/4/2019 | 1/7/2019 | 1/7/2019 | A | NH |
Matt Wrobel
|
|
|
Inspection requested via web by Margie Rowe
|