Information based on query as of Wednesday, July 3, 2024.
Permit Information
Permit NumberPLM19-01836
StatusIssued
Name DEBEST PLUMBING INC
Site Address 502 W FRONT ST
Project Name 
Customer Number19-02
ePlanReviewNo
Description
New: sanitary waste & vent piping, storm drains and leaders, domestic water and plumbing fixtures.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/13/20208/14/20208/13/2020APART
DetailsDaryl Spivey
TEMP FINAL FOR LAUNDRY ROOM - IF QUESTIONS CALL STEVE @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
temp occ ok for area requested for training.....ds
Plumbing Rough-in7/1/20207/1/20207/1/2020PPASS
DetailsDaryl Spivey
7th floor. if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
Plumbing Rough-in6/25/20206/25/20206/25/2020PPART
DetailsDaryl Spivey
waste ; water - 7th floor.
if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
hot water line in corridor tested ok...........ds
Plumbing Rough-in6/11/20206/12/20206/12/2020APASS
DetailsDaryl Spivey
rough-in water - rooms 602-613. if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
waste and vent rough in ok........ds
Plumbing Rough-in6/3/20206/3/20206/3/2020PPART
DetailsDaryl Spivey
waste- 6th street side 5th floor. if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
614 thru 624 waste and vent bathrooms tested thru 7th floor..........ds
Pressure Test6/2/20206/2/20206/2/2020PPASS
DetailsDaryl Spivey
Pressure Test - East Shaft Levels 1-7. If questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
Plumbing Rough-in5/26/20205/26/20205/26/2020PPART
DetailsDan Ediger
Rough-In Waste - If questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann.
402-413 and 502-513 r-in rr ok
Plumbing Rough-in5/12/20205/12/20205/12/2020PPART
DetailsDaryl Spivey
if questions call Steve @ ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann
partial 5th fl waste and partial 7th fl water..ds
Plumbing Rough-in5/11/20205/11/20205/11/2020PPART
DetailsDaryl Spivey
Waste inspection - if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
4th and 5th floors rooms 17,18,21,22,23,and 24 tested ok in ceilings......ds
Pressure Test4/28/20204/29/20204/29/2020ACANC
DetailsDaryl Spivey
water pressure test, if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
Plumbing Rough-in4/29/20204/29/20204/29/2020APART
DetailsDaryl Spivey
water pressure test, if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
rooms 314 thru 324 ok for cover and r/i is complete...........ds
Pressure Test4/14/20204/15/20204/15/2020PCANC
DetailsDaryl Spivey
water pressure test. if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
Plumbing Rough-in4/15/20204/15/20204/15/2020PPART
DetailsDaryl Spivey
water pressure test. if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
partial south side 5th, 6th and 7th...........ds
Plumbing Rough-in4/15/20204/15/20204/15/2020PCANC
DetailsDaryl Spivey
water pressure test. if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
south side 5th , 6th and 7th partial.....ds
Plumbing Rough-in4/13/20204/14/20204/14/2020APART
DetailsDaryl Spivey
water/waste/vent rough-in. if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
2nd and 3rd floor waste and 5th and 6th water partials............ds
Plumbing Rough-in3/30/20203/30/20203/30/2020PPART
DetailsDaryl Spivey
Above Ground Waste. If questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
2nd thru 4th floor 4 rooms on bathroom waste lines ok..........ds
Plumbing Rough-in3/26/20203/27/20203/27/2020ACANC
DetailsDaryl Spivey
above ground waste/vent. if questions call Steve @ ###-####. Phone #: ###-#### >> Inspection requested via web by Stacia Haumann Inspection cancelled from web by: Stacia Haumann
Plumbing Rough-in3/24/20203/25/20203/25/2020APART
DetailsDaryl Spivey
WASTE INSPECTION. If questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
kit waste 4th and 5th floors........ds
Pressure Test3/17/20203/17/20203/17/2020PPASS
DetailsDaryl Spivey
waste pressure test. if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
4th and 5th floor rms 14 thru 24 kit. walls only for w/v..........ds
Pressure Test3/9/20203/10/20203/10/2020APART
DetailsDaryl Spivey
Waste Pressure Test. If questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
2nd part of 6th and 7th floor waste on common walls for sinks only.............ds
Pressure Test3/6/20203/6/20203/6/2020PPART
DetailsDaryl Spivey
Waste Pressure Test - Street Side 6th ; 7th Floors. If questions please call Steve A. @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
Plumbing Rough-in2/18/20202/19/20202/19/2020APART
DetailsDaryl Spivey
WATER AND WASTE - If questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
laundry sink in laundry room ok.........ds
Other2/12/20202/12/20202/12/2020PPASS
DetailsDaryl Spivey
CONSULT - if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
went thru garage to look at getting TCO. needs tests on some garage drains and vents for SOI's
Other2/11/20202/12/20202/12/2020APART
DetailsDaryl Spivey
CONSULT - if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
Pressure Test1/27/20201/27/20201/27/2020PPART
DetailsDaryl Spivey
water ; waste pressure test - Rooms 206-215. If questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
2nd and 3rd floor south water and w/v........ds
Pressure Test1/22/20201/23/20201/23/2020APART
DetailsEric Strole
WATER ; WASTE PRESSURE TEST.
if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann-Sections inspected is marked on plans.
Pressure Test1/13/20201/13/20201/13/2020PPART
DetailsDaryl Spivey
water pressure test. if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
marked on plan..........ds
Pressure Test1/7/20201/8/20201/8/2020APART
DetailsDaryl Spivey
Domestic water pressure test. if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
marked on plan......ds
Roof Drains11/11/201911/12/201911/12/2019APART
DetailsDaryl Spivey
if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
roof drains tested and waste and vent tested ok om 1st floor up thru 2nd floor.........Laundry and pool room not done yet on 1st fl...........ds
Plumbing Rough-in10/16/201910/16/201910/16/2019PPART
DetailsDaryl Spivey
water/waste room 223. if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
Plumbing Rough-in10/2/201910/3/201910/3/2019APART
DetailsDaryl Spivey
waste. if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
west end hotel area under 2nd floor waste ok........ds
Plumbing Rough-in9/19/20199/23/20199/23/2019PPART
DetailsDaryl Spivey
rough-in waste. if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
west end under floor of 2nd floor......change k/s connections in horizontal for suds relief......ds
Groundwork5/24/20195/24/20195/24/2019PPART
DetailsDaryl Spivey
if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
south side bathroom.........ds
Groundwork5/14/20195/15/20195/15/2019APART
DetailsDaryl Spivey
if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
grease waste tested...........marked on plans in ESI office what has been inspected............ds
Groundwork5/13/20195/14/20195/14/2019APART
DetailsDaryl Spivey
grease interceptor - If questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
24 hr test on G/I ok and partial on sanitary east side west of seepage bed............ds
Groundwork5/10/20195/13/20195/13/2019APART
DetailsDaryl Spivey
grease interceptor - if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
24 hr test on G/I start and piping tested.......
Groundwork5/10/20195/10/20195/10/2019PPART
DetailsDaryl Spivey
if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
Groundwork5/8/20195/8/20195/8/2019PPART
DetailsDaryl Spivey
if questions call Steve @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
W/V on bathroom group ok...............ds
Final8/13/20208/18/2020 A 
DetailsDaryl Spivey
FINAL FOR FLOORS 2-4. IF QUESTIONS CALL STEVE @ ###-####. Phone #: ###-#### >> Inspection requested via web by Stacia Haumann