Permit Information
Permit NumberPLM19-05138
StatusFinaled
Name DRAIN PRO
Site Address 2273 S VISTA AVE Unit: STE 110
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: add gas line to rtu in 110
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/29/20201/29/20201/29/2020PPASS
DetailsEric Strole
Pressure Test1/16/20201/17/20201/17/2020APASS
DetailsEric Strole
Phone #: ###-#### Inspection requested via web by Jason Williams-60 lb gas test pass.
Final1/16/20201/16/20201/16/2020PNR
DetailsEric Strole
Phone #: ###-#### Inspection requested via web by Jason Williams
Final12/31/201912/31/201912/31/2019PFAIL
DetailsEric Strole
Phone #: ###-#### Inspection requested via web by Jason Williams-Need to resubmit plans for change to gas piping from approved plans. Need gas load calculations that are on gas line on new drawings. Will need to test gasline. If testing againt live system need two gas valves with open tee in the middle.
Pressure Test11/26/201911/27/201911/27/2019AFAIL
DetailsEric Strole
guage is located in unit 113 in ceiling Phone #: ###-#### Inspection requested via web by Jason Williams-Gas piping is not per the approved plans. See plans page P1.1 Key notes 13 & 14.