Permit NumberPLM20-01573
StatusFinaled
Name MIGUELS IRRIGATION & LANDSCAPING LL
Site Address 1024 W PARKHILL DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Backflow Preventer: install new backflow preventer
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Sprinkler (Final)4/20/20204/20/20204/20/2020PPASS
DetailsDaryl Spivey
Miguel **Cleared** Phone #: ###-####
Sprinkler (Final)4/16/20204/16/20204/16/2020PFAIL
DetailsDaryl Spivey
Meguil *cleared* Phone #: ###-####
dcva is not approved for installation on lawn sprinkler systems. PVB or a RPBP shall be installed with approved piping, connections and tested................ds