INSP - Final | 9/12/1996 | 9/12/1996 | 9/12/1996 | A | PASS |
Jim Soden
|
|
|
PASSED BY JSODEN CALLED ON CELL. TO CONFIRM
|
INSP - Final | 6/3/1996 | 6/3/1996 | 6/3/1996 | P | PART |
Jim Soden
|
|
|
06/03/96 347 - ON THE RESTURANT HOT WATER NOT ON-DUAL CHECKS FOR COFFEE MACHINES POST MIX UNITS NOT PIPE FROM RPS CLEANUT NEEDED ON WOMAN'S LAVATORY TEMP OCC. 6/3/6 347
|
PLM - Partial final | 4/30/1996 | 4/30/1996 | 4/30/1996 | P | PASS |
Jim Soden
|
|
|
04/30/96 347 - 1ST FLOOR partial final for perpetual metals o/k t.i.? 4/30/6 347
|
INSP - Final | 4/25/1996 | 4/25/1996 | 4/25/1996 | P | PART |
Jim Soden
|
|
|
04/25/96 347 - FINAL ON 2ND FLOOR O/K FOR FINAL OCCUPANCY 4/25/6 347
|
INSP - Plumbing Rough-in | 3/28/1996 | 3/29/1996 | 3/30/1996 | A | PASS |
Jim Soden
|
|
|
ROUGH IN ON 3RD AND 4TH FLOOR.
|
INSP - Plumbing Rough-in | 3/29/1996 | 3/29/1996 | 3/29/1996 | | FAIL |
Jim Soden
|
|
|
/ / 347 - DRAIN TEST FAILED 3/29/6 347
|
INSP - Plumbing Rough-in | 3/29/1996 | 3/29/1996 | 3/29/1996 | | PASS |
Jim Soden
|
|
|
/ / 347 - CORE AND SHELL ROUGH IN FINAL PASS
|
INSP - Plumbing Rough-in | 2/20/1996 | 2/21/1996 | 2/21/1996 | A | PART |
Jim Soden
|
|
|
02/20/96 347 - 2ND FLOOR BATHROOM
|
INSP - Plumbing Rough-in | 2/20/1996 | 2/20/1996 | 2/20/1996 | P | CANC |
Jim Soden
|
|
|
02/20/96 347 - 2ND FLOOR BATHROOM
|
INSP - Miscellaneous | 1/3/1996 | 1/3/1996 | 1/4/1996 | P | PART |
Gary Ziegler
|
|
|
01/03/96 334 - GREASE TRAP
|
INSP - Plumbing Rough-in | 12/4/1995 | 12/5/1995 | 12/5/1995 | A | PART |
Bill VanDegrift
|
|
|
12/04/95 330 - RESTAURANT partial r/i ok kitchen area
|
INSP - Plumbing Rough-in | 12/1/1995 | 12/1/1995 | 12/1/1995 | P | FAIL |
Lee Rice
|
|
|
gave correction notice to forman on the job, Hank Reader. Corections: 1. Repipe (4) floor drains with individual vents up through floor. (They were tied together below floor) and 2. replace 2" waste with 3" where fixture units exceed 8 FU's. this is on the line going to the grease trap. Commercial floor sinks are 3 FU'S.
|
INSP - Plumbing Rough-in | 11/29/1995 | 11/30/1995 | 11/30/1995 | A | CANC |
Jim Soden
|
|
|
11/30/95 347 - RESTAURANT AREA
|
INSP - Plumbing Rough-in | 11/15/1995 | 11/16/1995 | 11/16/1995 | A | PART |
Gary Ziegler
|
|
|
11/16/95 334 - PARTIAL R/I RESTROOMS ONLY /////////
|