Permit Information
Permit NumberBLD19-02943
StatusIssued
Name OPUS DESIGN BUILD LLC
Site Address 200 W MYRTLE ST
Project Name3rd & Myrtle Foundation
Customer NumberGRD19-00067
ePlanReviewYes
Description
***GREEN TAG-PRIORITY REVIEW-PROJECT MANAGEMENT-Angie Brosious***(3RD AND MYRTLE) (FOUNDATION AND FOOTING ONLY )*** Do not issue until grading permit GRD19-00067 is issued and ROS completed** Permit for foundation and utilities to include underground plumbing for an eight-story mixed-use residential housing project with structured parking and ground floor commercial space. No vertical construction is allowed. Shell/Core under BLD19-03238. Work is allowed to be done at the owners risk; any items found to be not in compliance upon approval of the plans shall be corrected prior to any further work being completed. Site grading permit under GRD19-00067. Special Inspections required per attached Form 310. **JAR**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Routing PW Flood Plain3/26/2020 3/26/2020 FAIL
DetailsJason C. Taylor
A portion of the subject property is within the regulatory floodplain. This project must comply with the Boise Floodplain Ordinance (B.C.C. 11-08). If you have any questions, please call Jason Taylor at ###-####.

Upload Elevation Certificates. Elevation Certificate elevations need to be placed on site plan, foundation plan, and cross section plans. Jason Taylor ###-####.
BLD-Footing1/9/20201/10/20201/13/2020ACANC
DetailsDave Hannah
Joe Phone #: ###-####
BLD-Footing12/19/201912/20/201912/23/2019APASS
DetailsDave Hannah
JOE Phone #: ###-####
BLD-Footing12/10/201912/11/201912/11/2019APART
DetailsDave Hannah
Pouring at 1pm-Joe Phone #: ###-#### ok after spec inspection sign offs
BLD-Foundation12/4/201912/4/201912/4/2019PPART
DetailsJim Storey
Joe Phone #: ###-#### placed w/si pending report.
BLD-Footing12/2/201912/3/201912/3/2019APART
DetailsMike Jordan
Joe Phone #: ###-####. Work in progress. Special inspector on site.
BLD-Foundation11/26/201911/27/201911/27/2019APASS
DetailsDave Hannah
Joe Phone #: ###-####
BLD-Foundation11/21/201911/25/201911/25/2019APASS
DetailsDave Hannah
Joe Phone #: ###-####
BLD-Footing11/19/201911/21/201911/21/2019PPART
DetailsDave Hannah
joe Phone #: ###-####
BLD-Concrete11/19/201911/20/201911/21/2019PPASS
DetailsDave Hannah
joe Phone #: ###-####
BLD-Other11/15/201911/19/201911/19/2019APASS
DetailsDave Hannah
pour at 2 // concrete columns // Joe Phone #: ###-####
BLD-Other11/15/201911/18/201911/18/2019APASS
DetailsDave Hannah
pour at 1 // concrete columns // Joe Phone #: ###-####
BLD-Footing11/13/201911/14/201911/18/2019PPASS
DetailsDave Hannah
poured columns // Joe Phone #: ###-####
BLD-Concrete11/13/201911/14/201911/18/2019APASS
DetailsDave Hannah
poured columns // Joe Phone #: ###-####
BLD-Footing11/6/201911/7/201911/8/2019PPASS
DetailsDave Hannah
Joe Phone #: ###-####
BLD-Conference10/25/201910/28/201910/29/2019ADONE
DetailsDave Hannah
joe Phone #: ###-####
BLD-Conference10/17/201910/18/201910/18/2019ADONE
DetailsMike Jordan
Joe Sonic Phone #: ###-####
Issue PAID IN FULL permit  10/16/2019 DONE
Telephone call  10/16/2019 DONE
Emailed permits to be signed to- tim.callahan@opus-group.com Eplan needs to be released
Inspection Record Card- Bld  10/16/2019 DONE
Telephone call  10/15/2019 DONE
PER TISHA okay to issue without ACHD see Doc_emailed- Emailed tim.callahan@opus-group.com to inform cust that ACHD Receipt or Fees need to be paid.
Permit Ready to Issue  10/3/2019 DONE
ALL MET SEE EMAIL FROM 10-16-19 Need
ACHD

MET
GC Form
Revised Value
Plan assigned to (JAR)8/14/20198/14/201910/2/2019 DONE
DetailsJulie Romig
09/30 - Reroute to DR/Add - 1st Rev Comp - **GREEN TAG** 3rd & Myrtle Footing/Foundation Only
PLANS/APPL TAKEN TO FRONT DESK  10/2/2019 DONE
Routing - PLAN CHECK9/17/2019 10/2/2019 PASS
DetailsJulie Romig
Do not issue until Grading Permit is issued. Bldg Review passed. Air rights and ROS finalized; route back to DR/Addressing for sign off.
Routing - Design Review9/27/2019 9/30/2019 PASS
DetailsJosh Wilson
Routing - FIRE9/17/20199/17/20199/27/2019 PASS
DetailsErika Akin
Attached comments to case
Routing - Addressing9/27/2019 9/27/2019 PASS
DetailsDoug Chausow
Routing PW Drainage9/17/2019 9/27/2019 PASS
DetailsBrian Murphy
Routing - Design Review9/17/2019 9/25/2019 FAIL
DetailsJosh Wilson
1. Air rights agreement with ACHD required, 2. Record of Survey combining parcels must be completed
Routing Off Site - STRUCTURAL9/17/2019 9/18/2019 PASS
DetailsJulie Romig
Routing - Addressing9/17/2019 9/17/2019 FAIL
DetailsDoug Chausow
All parcels need to be consolidated into 1
Route to Impact Fee Review9/3/20199/6/20199/4/2019 PASS
DetailsShannon Cade
Review requested for Commercial Permit
Routing - PLAN CHECK8/14/2019 9/3/2019 FAIL
DetailsJulie Romig
Refer to ePlanReview for required corrections.
Routing Off Site - STRUCTURAL8/14/2019 9/3/2019 FAIL
DetailsJulie Romig
Jacobs
1st review completed  9/3/2019 FAIL
DetailsJulie Romig
Routing - FIRE8/14/20198/14/20198/29/2019 FAIL
DetailsErika Akin
Attached comments to case and emailed architect
Routing PW Environmental8/15/2019 8/27/2019 PASS
DetailsRick Christenson
Pretreatment needs to review plans with grease abatement for listed cafe
Routing - Design Review8/14/2019 8/26/2019 FAIL
DetailsJosh Wilson
1. Air rights agreement with ACHD required, 2. Shell/core permit must be submitted prior to sign off on foundation permit
Routing PW Drainage8/15/2019 8/22/2019 FAIL
DetailsBrian Murphy
NEED GRADING PLAN APPROVAL
Routing PW Street Lights8/15/2019 8/19/2019 PASS
DetailsTom Marshall
Streetlight plans should be on the next BLD submitted.
Routing - Erosion and Sediment8/14/2019 8/16/2019 PASS
DetailsMichael Zawacki
Please refer to ESC19-00292 attached to grading and drainage permit.
Routing - MECHANICAL8/14/2019 8/16/2019 PASS
DetailsTroy James
No mechanical to review at this time.
Routing - PLUMBING8/14/2019 8/15/2019 PASS
DetailsDaryl Spivey
Per plan and ISPC.
Routing - PLANNING8/14/2019 8/15/2019 PASS
DetailsDavid Moser
SEE DRH19-00007
Routing - Addressing8/14/2019 8/15/2019 FAIL
DetailsDoug Chausow
Individual parcels need to be conolidated into 1.
Routing - PUBLIC WORKS8/14/2019 8/15/2019 PASS
DetailsMorgan Webb
Routing PW Sewer Design8/15/2019 8/15/2019 PASS
DetailsDeAnn Brown
Routing PW Solid Waste8/15/2019 8/15/2019 PASS
DetailsEvan Carpenter
Intake Approval  8/14/2019 PASS
DetailsMichael Hanson
Intake Approval  8/7/2019 FAIL
DetailsMichael Hanson
1. #310 form is incomplete - Complete all fields on cover sheet including permit number, owner information, owner signature.
2. Structural sheets are missing the Idaho registered design professional stamp, signed and dated. please resubmit all structural sheets for approval with this stamp, signed and dated.
Application received  8/2/2019 DONE
Application submitted via PDS Online on Aug 2 2019 11:19AM