Information based on query as of Tuesday, May 14, 2024.
Permit Information
Permit NumberELE19-02231
StatusFinaled
Name PARK RICH A
Site Address 1505 E JEFFERSON ST
Project NamePark remodel
Customer Number 
ePlanReviewNo
Description
Addition
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/29/20201/30/20201/30/2020PPASS
DetailsJames Ady
Rich Phone #: ###-#### corrections made final ok
Final1/22/20201/23/20201/23/2020PFAIL
DetailsJames Ady
richard Phone #: ###-#### Laundry room counter recep dead, 2 pole Lock out needed for Water heater breaker
Electrical Rough-In7/15/20197/16/20197/17/2019PPASS
DetailsJames Ady
Rich Phone #: ###-#### Rough in of M. Bed, M. Bath, Laundry room and geust bed ok to cover
Electrical Rough-In7/11/20197/15/20197/15/2019AFAIL
DetailsJames Ady
Rich Phone #: ###-#### Finish make up(Pigtail receps and switches, finish all attic j-boxes) Swap dryer box with listed 2gang box. Move all staples to outside of 1 1/4in from face of stud. Install smoke detectors per code.
Conference6/17/20196/19/20196/19/2019APASS
DetailsJames Ady
Rich Phone #: ###-#### Customer adding Master bed, bath and closet as well as 1 bed and a laundry room. Discussed 20A for laundry, 20A for Bath vanity, 30A for dryer, AFCI for beds, Tamper resistant receps for all locations. Adding Furnace in crawl. Will require Light and recep, both will need GFCI protection.
Application received  6/17/2019  
Issue PAID IN FULL permit  6/17/2019 DONE