Permit Information
Permit NumberELE19-02467
StatusFinaled
Name CORNERSTONE ELECTRIC
Site Address 4503 W IRVING ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: Remodel/addition-adding 1 perm service up to 200 AMP and 21 new branch circuits which includes 1 for a futur hot tub
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/17/201910/17/201910/17/2019PPASS
DetailsEric Story
###-####
Final ok
Final10/7/201910/7/201910/7/2019PFAIL
DetailsRock A. Hudson
Cal Phone #: ###-####
110.3- Faceless GFCI device in laundry will not reset or trip.
314.25- All boxes shall have covers. Basement ceiling.
As per parcel note unable to final until street light repair complete.
All other areas in house checked out ok
Override - Parcel Holds10/7/20191/1/190010/7/2019  
this is not the building final
Electrical Rough-In7/15/20197/15/20197/15/2019PPASS
DetailsRock A. Hudson
Cal- inspection for ground wire Phone #: ###-####
Grounding electrode conductor rough in ok cover
Override - Parcel Holds7/15/20191/1/19007/15/2019  
this inspection has nothing to do with the street lights that the builder needs to fix.
Rough-In Permanent Service7/4/20197/5/20197/5/2019APASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by cal crosby
Rough-in ok to cover
p/s o/h n ok
Electrical Rough-In7/2/20197/2/20197/2/2019PPASS
DetailsJames Ady
Cal- groundning inspection Phone #: ###-#### 25ft #4 bare along footing to be used as concrete encased electrode ok to cover
Issue PAID IN FULL permit  7/2/2019 DONE
Payment received via Govolutions
Application received  7/2/2019 DONE
This permit was created on the web by cal crosby
Telephone call  7/2/2019 DONE
customer called and will call back with the fixture count for this project-called back added fixtures and hot tub