Information based on query as of Thursday, October 31, 2024.
Permit Information
Permit NumberFIR16-00708
StatusFinaled
Name MOUNTAIN ALARM
Site Address 1093 S HILTON ST
Project NameHillcrest Assisted Living
Customer Number 
ePlanReviewYes
Description
Replacing existing Pyrotronics fire system with Notifier fire system. This project does not appear to be associated with a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/31/20186/7/20186/7/2018APASS
DetailsTroy Cobbley
Permit finaled. The wet and dry systems were tested today., Devices for elevator recall in place but elevators are incapable of recall at this time.


Ray McQueen, inspecting technician, building is open for access Phone #: ###-#### Inspection requested via web by Rose Peterson
INSP-Final Inspection5/31/20186/6/20186/4/2018ACANC
DetailsTroy Cobbley
Ray McQueen, inspecting technician, building is open for access Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
INSP-Final Inspection5/31/20186/4/20186/4/2018PFAIL
DetailsTroy Cobbley
Today was a partial inspection. See Lee's entry for items tested.


Ray McQueen, inspecting technician, building is open for access Phone #: ###-#### Inspection requested via web by Rose Peterson
Inspection6/4/20186/4/20186/4/2018PPART
DetailsLee G Meredith
Restest of 3 failed horn strobes, 1 kitchen hood and 1 relocated smoke detector that was too close to fans. All passed.
INSP-Final Inspection5/25/20185/31/20185/31/2018AFAIL
DetailsTroy Cobbley
Partial inspection today. See Lee's entry for items tested/inspected.

Tank, inspecting technician, building is open access Phone #: ###-#### Inspection requested via web by Rose Peterson
Inspection5/31/20185/31/20185/31/2018APART
DetailsLee G Meredith
Tested dwelling unit detectors and sounders. Tested notification. Two areas need to be addresses. 2nd floor had horns that did not provide temporal signal, 1st floor had one horn in an admin office that did not sync.
INSP-Final Inspection5/25/20185/30/20185/30/2018AFAIL
DetailsTroy Cobbley
Partial inspection today. See entry by Lee for items tested today.

Nick Tank, inspecting technician, building is open access Phone #: ###-#### Inspection requested via web by Rose Peterson
Inspection5/30/20185/30/20185/30/2018APART
DetailsLee G Meredith
Tested corridor smokes, mag door holds and all pull stations.
Miscellaneous action  5/30/2018 DONE
Received and reviewed as built drawings showing a substitution for the panel and communicator. These are acceptable and I emailed Rose to inform her.
INSP-Final Inspection5/25/20185/29/20185/29/2018AFAIL
DetailsTroy Cobbley
Today was a partial inspection. We verified that all off the redlined corrections had been made and are shown on the plan modification. The two items that had been missed was the data sheet approved did not match the fire alarm control panel installed and the dialer was not approved/shown. When these two items have been approved we can begin testing of the devices.


Nick Tank, inspecting technician, building is open access Phone #: ###-#### Inspection requested via web by Rose Peterson
Plan Modification Accepted  5/14/2018 DONE
Alarm Plan Check5/14/2018 5/14/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  5/14/2018 DONE
Plan mod approved. No additional review comments.
Permit Ready to Issue  5/14/2018 DONE
plan mod-please don't re issue
CHANGE STATUS TO (ISS)  5/14/2018 DONE
INSP-Final Inspection3/28/20183/29/20183/29/2018PDONE
DetailsTroy Cobbley
Today I did a walk thru of the second floor. See the city approved plans for sheet signed and dated and with corrections noted in red. The corrections noted are not an absolute list of all items that may need attention. The contractor shall verify that system installation will meet minimum code compliance. The walk thru over the last couple of days did not include the actual testing of any devices. Plan modifications and corrections made in the field will be needed prior to testing of devices.

Nick Tank, inspecting technician Phone #: ###-#### Inspection requested via web by Rose Peterson
INSP-Final Inspection3/27/20183/28/20183/28/2018PDONE
DetailsTroy Cobbley
Today we finished the walk thru for the first floor. See the approved plans that have been dated and signed for the specific areas looked at. I noted added horn/strobes and areas where horn/strobes need to be added. Possibly a manual pull station will need to be added in a stairwell. Plan modifications will be needed.

Ray McQueen, inspecting technician Phone #: ###-#### Inspection requested via web by Rose Peterson
INSP-Final Inspection3/21/20183/27/20183/27/2018ADONE
DetailsTroy Cobbley
Today was a partial inspection. I looked at the control equipment and one first floor wing of the system. I noted that a different FACP panel has been installed, a different communication method has been installed, of the nine NAC panels installled two are different from the rest, all nine are triggered from a single module which is not shown on the plans, the trouble signals are being monitored by two monitor modules that are not shown on the plans, breaker lock is missing, one wall mounted a/v is overspaced as marked on plans, notification needs to be added in the Office with three people in it as marked on the plans. Again this was a partial inspection.

Ray McQueen, inspection technician; building has open availability Phone #: ###-#### Inspection requested via web by Rose Peterson
Telephone call  3/27/2018 DONE
Troy called to note there is a beam that exceed 10% of the ceiling heign between the kitchen and living room. He wanted to know if this would require multiple detectors. per 2013 NFPA 72 17.7.3.2.4.2 (5) a single detector is acceptable if the room is under 900 ft. squared. Drawings indicate the rooms are approximately 235 ft squared so this appears to be adequate.
INSP-Final Inspection3/8/20183/15/20183/15/2018ACANC
DetailsTroy Cobbley
Ray McQueen, inspecting technician Open building access Phone #: ###-#### Inspection requested via web by Rose Peterson
Miscellaneous action  3/15/2018 DONE
As Built drawings received.
Alarm Plan Check3/15/2018 3/15/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/15/2018 DONE
As built drawings approved. No fees to be charged.
CHANGE STATUS TO (ISS)  3/15/2018 DONE
(F) Reprint permit  3/15/2018 DONE
Miscellaneous action  12/11/2017 DONE
3 new product data sheets were for wireless detectors. I emailed Rose to let her know that we currently don't allow wireless devices. She is checking to see if the product data was submitted in error.
Miscellaneous action  12/8/2017 DONE
Rose emaile a request to open the workflow for a plan modification upload.
Alarm Plan Check11/15/2016 11/15/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  11/15/2016 DONE
Plans approved with review comments and drawing notation.
Permit Ready to Issue  11/15/2016 DONE
Issue and Print Permit  11/15/2016 DONE
Inspection Record Card- Fire11/15/2016 11/15/2016 DONE
DetailsKristal Soland
Plan resubmittals received  11/14/2016 DONE
Miscellaneous action  11/14/2016 DONE
Emailed Rose Peterson to inform her that the resubmittal is being returned, without review, due to new files with names that are different that original file names.
Plan resubmittals received  11/14/2016 DONE
Miscellaneous action  11/14/2016 DONE
Emailed Rose to request product data for non-addressable smoke detectors shown in dining room.
1st review completed  11/3/2016 FAIL
Drawings submitted as a single file. Failed pre-screen review and notified Rose that files need to be uploaded individually.
Plan assigned to (Lee)11/3/2016 11/3/2016 DONE
DetailsLee G Meredith
Plan resubmittals received  11/3/2016 DONE
1st review completed  11/3/2016 FAIL
See 1st review comments.
Miscellaneous action  11/3/2016 DONE
Emailed review comments to Rose Peterson.
Application received  11/2/2016 DONE
Application submitted via PDS Online on Nov 2 2016 2:52PM