Information based on query as of Monday, May 20, 2024.
Permit Information
Permit NumberFIR18-00830
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 2061 S HUDSON AVE
Project NameSkyline Apartments Bldg J
Customer Number 
ePlanReviewYes
Description
[Skyline Apartments Building J]
The fire sprinkler scope of work consists of installing a new fire sprinkler system into a new three-level apartment building per NFPA 13R, 2016, and the City of Boise. The system has floor control valves, residential sprinklers and CPVC piping.

• The underground piping is under permit FIR18-00812

[BLD17-04630]
Building J: (SKYLINE APARTMENTS – BUILDING TYPE 2, Building A, B, C, E, G and J) (24 units) PLAN MOD RELOCATE WASHER/DRYER FROM BATHROOM TO HALLWAY ADD CLOSED DOOR AS NOTED ON APPROVED PLANS 7-2-18**AJS**The NFPA 13-R fire sprinkler system is used for occupancy and for story increase. To construct a 25,320 square foot three story VB Type of Construction apartment building (8,458 sq. ft. 1st story and 8,431 sq. ft. 2nd story and 8,431 sq. ft. 3rd story). Each unit is 1 story. Work is to include concrete footings, concrete foundations, concrete slabs on grade, wood stud bearing walls, wood stud shear walls, fiberglass shingles, 1-hr dwelling unit separations, 1-hour fire barriers for stair and breezeways, rated doors in breezeway, interior nonbearing walls, millwork, and finishes. Special Inspection is NOT required. The roof truss design is a deferred submittal item. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13-R as regulated by the Fire Department. Separate fire sprinkler permits shall be obtained prior to beginning any modification or installation work on such systems. **ajs**192-unit apartment project with (9) apartment buildings, clubhouse, and associated site work

Alternative Materials and Methods:
This project includes approved code alternates to the following fire protection systems and/or building life safety systems. Please review the supplemental documents attached to this building permit case for details. Fire protection “shop drawings” shall include approved code alternate design.

• There are no AMM at this time.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/28/20198/29/20198/29/2019PPASS
DetailsJim Page
Previously noted item has been corrected, final fire sprinkler inspection complete.

Jon Beazer is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection8/26/20198/28/20198/28/2019PFAIL
DetailsJim Page
Level 1 flow switch did not operate correctly during waterflow, flow switch would not go into alarm automatically.

Jon Beazer is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in4/18/20194/19/20194/19/2019APASS
DetailsJim Page
Tenting inspection for level 3 complete, all tenting in place at time of inspection, level 3 sprinkler piping approved for cover.

Jon Beazor is the contact. He wishes this to be a tenting inspection. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro4/16/20194/17/20194/17/2019PDONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Jon Beazor is the contact. He wants this to be a hydro only. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in3/12/20193/13/20193/13/2019PPART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping complete, levels 1 and 2 approved for cover, tenting still needs to be installed on 3.

Gerardo Arce is the contact. Thank you for your work! Phone #: ###-#### Inspection requested via web by Stan Beus
Intake Approval  10/31/2018 PASS
DetailsTim Frost
Plan assigned to (Tim)10/31/2018 10/31/2018 DONE
DetailsTim Frost
Sprinkler Plan Check10/31/2018 10/31/2018 PASS
DetailsTim Frost
Please, see attached comments.
1st review completed  10/31/2018 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  10/31/2018 DONE
DetailsTim Frost
Permit Ready to Issue  10/31/2018 DONE
all requirements met
Issue and Print Permit  10/31/2018 DONE
Application received  10/27/2018 DONE
Application submitted via PDS Online on Oct 27 2018 3:01PM