INSP-Final Inspection | 10/15/2019 | 10/17/2019 | 10/17/2019 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. Previous corrections addressed.
Phone #: ###-#### Inspection requested via web by Jason Heath
|
INSP-Final Inspection | 10/10/2019 | 10/11/2019 | 10/11/2019 | P | FAIL |
Jim Page
|
|
|
Audio visual devices in restrooms did not function. Smoke detector in room 6 is within 36 inches of HVAC register, relocate detector as discussed.
Phone #: ###-#### Inspection requested via web by Jason Heath
|
Plan resubmittals received | | | 10/10/2019 | | DONE |
|
|
|
|
Intake Approval | | | 10/10/2019 | | PASS |
|
|
|
|
1st review completed | | | 10/10/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 10/10/2019 | | 10/10/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 10/10/2019 | | DONE |
|
|
|
As built - No fee.
|
Permit Ready to Issue | | | 10/10/2019 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 10/10/2019 | | DONE |
|
|
|
|
Plan resubmittals received | | | 10/9/2019 | | DONE |
|
|
|
as built per Jason-started workflow in e plan
|
Plan assigned to (Lee) | 10/9/2019 | | 10/9/2019 | | DONE |
Lee G Meredith
|
|
|
as built per Jason Heath
Returned to jason for file name correction.
|
Plan assigned to (Lee) | 6/17/2019 | | 6/18/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 6/18/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 6/17/2019 | | 6/18/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 6/18/2019 | | DONE |
|
|
|
Passed with requirements.
|
Permit Ready to Issue | | | 6/18/2019 | | DONE |
|
|
|
met
|
Issue and Print Permit | | | 6/18/2019 | | DONE |
|
|
|
|
Application received | | | 6/17/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 17 2019 1:53PM
|