INSP-Final Inspection | 10/23/2019 | 10/24/2019 | 10/24/2019 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
CHANGE STATUS TO (ISS) | | | 10/22/2019 | | DONE |
|
|
|
plan mod
|
Plan Modification Accepted | | | 10/21/2019 | | DONE |
|
|
|
change to release door holders using corridor area detection at the corridor side of doors. the other side of doors is unchanged (using single smoke detector with relay)
|
Plan assigned to (Lee) | 10/21/2019 | | 10/21/2019 | | DONE |
Lee G Meredith
|
|
|
|
Plan Modification Accepted | | | 10/21/2019 | | DONE |
|
|
|
|
1st review completed | | | 10/21/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 10/21/2019 | | 10/21/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 10/21/2019 | | DONE |
|
|
|
Plan mod approved. Review fee is $65 (min. fee)
|
Permit Ready to Issue | | | 10/21/2019 | | DONE |
|
|
|
|
INSP-Final Inspection | 10/16/2019 | 10/17/2019 | 10/17/2019 | A | FAIL |
Troy Cobbley
|
|
|
Tested all devices but the new smoke detector in the main corridor is not centered on the doors as required in nfpa 72.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
Application received | | | 9/10/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Sep 10 2019 7:10AM
|
Plan assigned to (Lee) | 9/10/2019 | | 9/10/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 9/10/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 9/10/2019 | | 9/10/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 9/10/2019 | | DONE |
|
|
|
Quick permit passed. No comments.
|
Permit Ready to Issue | | | 9/10/2019 | | DONE |
|
|
|
|
Issue and Print Permit | | | 9/10/2019 | | DONE |
|
|
|
|