Final | 12/19/2018 | 12/20/2018 | 12/20/2018 | A | PASS |
Brian Scoles
|
|
|
re final code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- final ok
|
Final | 12/14/2018 | 12/17/2018 | 12/17/2018 | P | FAIL |
Brian Scoles
|
|
|
Garage Code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- need access into house all doors locked up garage code worked- need 3 screws in water heater flue to china cap in garage- need to seal lineset penetration outside at a/c location-
|
Conference | 10/23/2018 | 10/24/2018 | 10/24/2018 | A | PASS |
Brian Scoles
|
|
|
Witness blast 1130. I will make sure my guys have a ladder Phone #: ###-#### Inspection requested via web by Randy Hart- duct blast test pass
|
Rough-in | 10/24/2018 | 10/24/2018 | 10/24/2018 | A | PASS |
Brian Scoles
|
|
|
Witness blast 1130. I will make sure my guys have a ladder Phone #: ###-#### Inspection requested via web by Randy Hart- R/I ok
|
Rough-in | 10/23/2018 | 10/23/2018 | 10/23/2018 | P | FAIL |
Brian Scoles
|
|
|
Rough and pressure Phone #: ###-#### Inspection requested via web by Randy Hart- still need city approved manual J onsite to do inspection- send one with duct blast guys thats scheduled for tomorrow
|
Pressure Test | 10/23/2018 | 10/23/2018 | 10/23/2018 | P | PASS |
Brian Scoles
|
|
|
Rough and pressure Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass
|
Rough-in | 10/19/2018 | 10/22/2018 | 10/22/2018 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- need approved manual J onsite- need nail plates on primary pvc drain- all register boots need sealed with mastic on inside- exhaust fan connections need sealec to fan- all rips and tears inarma flex need fixed bare copper showing 2nd floor at ceiling
|
Pressure Test | 10/19/2018 | 10/22/2018 | 10/22/2018 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- gauge under 20psi
|
Issue PAID IN FULL permit | | | 10/19/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/19/2018 | | DONE |
|
|
|
This permit was created on the web by Randy Hart
|