Final | 2/7/2019 | 2/8/2019 | 2/8/2019 | P | PASS |
Brian Scoles
|
|
|
code 2468 Re- Inspection Phone #: ###-#### Inspection requested via web by Randy Hart- HVAC and fireplace final ok
|
Final | 2/6/2019 | 2/7/2019 | 2/7/2019 | A | FAIL |
Brian Scoles
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- need uv protection on lineset at condenser location- need to seal gas line penetration at meter into house outside
|
Conference | 12/26/2018 | 12/26/2018 | 12/26/2018 | P | PASS |
Brian Scoles
|
|
|
meet at 130 for duct blast witness- duct blast test pass
|
Conference | 12/21/2018 | 12/26/2018 | 12/26/2018 | A | NR |
Brian Scoles
|
|
|
Witness blast verified with Brian for the 26th @ 11:15 am Phone #: ###-#### Inspection requested via web by Randy Hart- no one there at time scheduled
|
Pressure Test | 12/18/2018 | 12/19/2018 | 12/19/2018 | A | PASS |
Brian Scoles
|
|
|
re inspection Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass
|
Rough-in | 12/18/2018 | 12/19/2018 | 12/19/2018 | A | PASS |
Brian Scoles
|
|
|
re inspection Phone #: ###-#### Inspection requested via web by Randy Hart- R/I ok- fireplace R/I ok
|
Rough-in | 12/19/2018 | 12/19/2018 | 12/19/2018 | A | PASS |
Brian Scoles
|
|
|
re inspection Phone #: ###-#### Inspection requested via web by Randy Hart- fireplace R/I ok
|
Rough-in | 12/14/2018 | 12/17/2018 | 12/17/2018 | A | FAIL |
Brian Scoles
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- need approved stamped man j onsite for inspection- need to mastic/seal inside all boots supply and return- water heater b vent needs 1" clearance to truss in attic- square supply duct nw room needs insulated on square to round end cap in attic- need ladder provided to access furnace and coil in attic- need to support dryer duct every 4'- need to fix all rips and tears in arma flex whole lineset- who installed fireplace? if you did please add to description on notes- need another strap on supply duct in hallway from garage register is sagging- left correction notice front entry window
|
Pressure Test | 12/14/2018 | 12/17/2018 | 12/17/2018 | A | FAIL |
Brian Scoles
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- gauge below 20psi
|
Issue PAID IN FULL permit | | | 12/14/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/14/2018 | | DONE |
|
|
|
This permit was created on the web by Randy Hart
|