Final | 2/21/2019 | 2/22/2019 | 2/22/2019 | A | PASS |
Ben Livingston
|
|
|
robin # ###-#### Phone #: ###-#### Inspection requested via web by Robin Cox
|
Rough-in | 2/12/2019 | 2/12/2019 | 2/12/2019 | P | PASS |
Ben Livingston
|
|
|
FYI open lines were from abandoned fan coil. they have been crimped and bent back Phone #: ###-#### Inspection requested via web by Robin Cox above cieling okay
|
Rough-in | 2/8/2019 | 2/11/2019 | 2/11/2019 | P | FAIL |
Ben Livingston
|
|
|
cover, want to drop tile. FYI, I have air balance scheduled Monday as well Phone #: ###-#### Inspection requested via web by Robin Cox flex needs to be strapped up off grid, not all line sets have armaflex and need to be attached to hangers, one of the linesets are still open, condensate 2nd drain hung up on light
|
Rough-in | 1/17/2019 | 1/18/2019 | 1/18/2019 | A | PASS |
Ben Livingston
|
|
|
duct seal. stamped drawing is on plan table in vitam Phone #: ###-#### Inspection requested via web by Robin Cox duct seal pass
|
Rough-in | 1/16/2019 | 1/16/2019 | 1/16/2019 | P | FAIL |
Ben Livingston
|
|
|
duct seal inspection Phone #: ###-#### Inspection requested via web by Robin Cox need to have city stamped prints on site for inspection
|
Issue PAID IN FULL permit | | | 1/11/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/11/2019 | | DONE |
|
|
|
This permit was created on the web by Robin Cox
|
First Notice | 2/22/2019 | 2/22/2019 | | | |
Ben Livingston
|
|
|
|