Final | 10/16/2019 | 10/18/2019 | 10/18/2019 | P | PASS |
Brian Scoles
|
|
|
Please inspect from 12;30-4. Homeowner Fauzia Aziz ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- a/c coil co locking caps ok
|
Final | 10/4/2019 | 10/11/2019 | 10/11/2019 | P | NH |
Jack Reynolds
|
|
|
Please inspect after 1 PM. Fauzia Aziz ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette - no access to home left notice on front door
|
Final | 9/13/2019 | 9/20/2019 | 9/20/2019 | P | FAIL |
Brian Scoles
|
|
|
Homeowner Fauzia Aziz ###-####. Phone #: ###-#### Inspection requested via web by Mary LaFayette- need to install secondary wet switch- need to firecaulk primary drain in furnace closet at floor- need to change breaker in panel to meet min/max rating on a/c- has 15 amps now and minimum is 17.6- will need electrical permit issued by final for breaker swap
|
Issue PAID IN FULL permit | | | 9/11/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/11/2019 | | DONE |
|
|
|
This permit was created on the web by Mary LaFayette
|