Information based on query as of Monday, May 20, 2024.
Permit Information
Permit NumberMEC20-00387
StatusFinaled
Name MCFATE HEATING SERVICE
Site Address 2918 E EASTGATE DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: Install mini split, new venting
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/8/20204/9/20204/9/2020APASS
DetailsJack Reynolds
Our technician sent you pictures of the final requirements and we changed the permit to reflect the work done. Call ###-#### if you need the pictures resent. Thank you! Phone #: ###-#### Inspection requested via web by Dan McFate
- final ok
Final3/23/20203/24/20203/24/2020PPART
DetailsJack Reynolds
please call 30 minutes before you come thanks Phone #: ###-#### Inspection requested via web by Dan McFate
- adjust permit to show work that was done onsite
- penetrations need sealed
- talked with homeowner about gas line he stated the gas line was deleted from the project and will be done in the future.
Rough-in2/11/20202/12/20202/12/2020APASS
DetailsJack Reynolds
Call when you are on the way so we can be sure someone is there Phone #: ###-#### Inspection requested via web by Dan McFate
- gas line installation hasn't been started yet. schedule pressure test when ready
- permit needs to be adjusted to match work being done
- UL listed connector for plastic coated MC cable installed by final
Rough-in2/10/20202/11/20202/11/2020PFAIL
DetailsJack Reynolds
Call when you are on the way so we can ensure someone is there Phone #: ###-#### Inspection requested via web by Dan McFate
- dryer vent needs to be installed in a 2x6 wall as to not smash vent pipe
- line set insulation at indoor unit needs finished
- line set and condensate in crawl need supported
- exhaust fan flex ducting needs rip repaired
- gas line has not been installed yet will need to see pressure test when finished
- plastic coated MC cable for mini split needs UL listed connector installed by final
- adjust permit details to show all items being installed like dryer vent, one exhaust fan, and one A/C for mini split , and gas line which is already in the details
Issue PAID IN FULL permit  1/27/2020 DONE
Payment received via Govolutions
Application received  1/27/2020 DONE
This permit was created on the web by Dan McFate