Permit Information
Permit NumberBLD17-00359
StatusFinaled
Name THE ROBINS & MORTON GROUP
Site Address 8800 W EMERALD ST
Project NameTreasure Valley Hospital - A
Customer Number 
ePlanReviewYes
Description
**Project Management-Ron Hill** (TREASURE VALLEY HOSPITAL – REMODEL AND ADDITION – PACKAGE A) (DRH16-00514) (CUP16-00094) To complete Package A of a project to construct a 13,921 square foot addition to connect an existing 44,000 square foot hospital to an existing 13,500 square foot office building (about 1,500 square feet of the existing 15,000 square foot office building will be demolished to facilitate the addition). A 3-hr fire wall will be constructed to separate the Type I-B construction (about 57,921 square feet) from the Type V-B construction (about 13,500 square feet). This is a 2 package project. This permit is for concrete footings, concrete foundations, concrete slabs on grade, steel columns, steel beams, steel roof joists, steel roof deck, and a 3-hr masonry fire wall/smoke barrier wall. The building shell and interior tenant improvement work will be completed under future Package B. Special Inspection is required for soils, concrete, masonry, steel (including welding and bolting), and anchors post installed in hardened concrete. The design for the structural steel connections, exterior curtain walls, and steel stud connections to the structure are deferred submittal items. The work is required to comply with the approved drawings, with the structural design, with the plan review report, and with all applicable codes and ordinances. The submitted interior architectural drawings are for reference only and have not been approved. This permit does not establish a Certificate of Occupancy for any portion of the addition. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled  11/1/2018 DONE
Per BLD-Final Passed inspection (required signatures say no for c of o)
BLD-Final10/30/201810/31/201810/31/2018APASS
DetailsMike Jordan
Charles Phone #: ###-####. Ok for perm occ.
FIRE-Final Inspection10/30/201810/30/201810/30/2018PPASS
DetailsTroy Cobbley
life safety passed

Charles Phone #: ###-####
BLD-Framing/Rough-in4/27/20184/30/20184/30/2018PPASS
DetailsMike Jordan
Charles Phone #: ###-####. Interior steel stud framed walls at locker rooms.
BLD-Framing/Rough-in12/21/201712/21/201712/21/2017APASS
DetailsMike Jordan
Interior steel stud framed walls and soffits, remainder of addiotion ok.
BLD-Framing/Rough-in9/5/20179/6/20179/6/2017PPASS
DetailsMike Jordan
Jeff Phone #: ###-####. Interior steel stud framed walls for laundry room.
BLD-Foundation8/18/20178/21/20178/21/2017APART
DetailsMike Jordan
Jeff-rebar Phone #: ###-####. Footings and column pad footings at gridlines N7 from grids NB to NA. Grid NA from N4 to N7. Grid NA from N2 to N3. Noted some clearance issues. Will have special inspection. Special inspector to verify clearance issues are resolved.
BLD-Foundation8/10/20178/14/20178/14/2017APASS
DetailsMike Jordan
Rebar// Charles Phone #: ###-####. Footings and column pad footings on grid N6 from grids NG to NB.
BLD-Concrete8/7/20178/8/20178/8/2017PPASS
DetailsMike Jordan
rebar- Jeff Phone #: ###-####. Stemwalls on grid NM from grids N2-N4. Interior column pad footings on grid N4 at grids NG, NF and NC.
BLD-Foundation8/1/20178/2/20178/2/2017PPASS
DetailsMike Jordan
Interior column moment frame footings on grids N2 and N3 are now per detail 1/S5.10. Footings and column pad footings on gridline NM from N1 to N4, and N4 from NM to NH and NH from N4 to N7 are ok to place. Will also have specail inspection.
BLD-Foundation8/1/20178/1/20178/1/2017PCANC
DetailsMike Jordan
Rebar inspection. Moved to pm on 8-2-17.
BLD-Footing7/21/20177/24/20177/24/2017APART
DetailsMike Jordan
F6 type interior column pad footings ok to place. F7T and F8T interior column pad footings missing 33 ties and additional #4 next to anchor bolts. Noted all footings with T designation are moment frmae footings and require the additional rebar per detail 1 in S5-10. Verified with engineer of record. ok to place the F6 footings only.
BLD-Footing7/21/20177/21/20177/21/2017PCANC
DetailsMike Jordan