Permit Information
Permit NumberBLD18-00105
StatusFinaled
Name ANDY THOMPSON CONSTRUCTION INC
Site Address 9339 W CORY LN
Project NameAventura West
Customer NumberBLD18-00102-105, 03811; ESC18-00031
ePlanReview 
Description
(AVENTURA WEST) (4 PERMITS FILED UNDER BLD18-00102 IN EPLANREVIEW)
Permit for the construction of 4 multi-family buildings consisting of 16 units total (4) fourplexes, along with associated site work including a 144 sq ft pavilion under BLD18-03811. The fourplexes are reviewed under the 2012 IBC and are required to be fire sprinklered with an NFPA 13R system. JAR
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final9/13/20199/16/20199/16/2019PPASS
DetailsTell Riley
Andy Phone #: ###-####//final complete//
FIRE-Final Inspection9/13/20199/16/20199/16/2019APASS
DetailsMike Jordan
Andy Phone #: ###-####. The project related fire sprinkler permit has been finaled.
FIRE-Final Inspection8/20/20198/21/20198/21/2019APART
DetailsTroy Cobbley
Life safety temp until the project related fire sprinkler system is finaled.

Phone #: ###-#### Inspection requested via web by Andy Thompson
BLD-Final8/19/20198/19/20198/19/2019PPART
DetailsTell Riley
Phone #: ###-#### Inspection requested via web by Andy Thompson//window fall protection added//occupancy ok for 1 week in conjunction with fire life safety//after fire signs off-occupancy ok//
BLD-Final8/15/20198/15/20198/15/2019PFAIL
DetailsTell Riley
please call 1st Phone #: ###-#### Inspection requested via web by Andy Thompson//add window fall prtection devices per plans//
FIRE-Final Inspection8/14/20198/14/20198/14/2019PPART
DetailsTroy Cobbley
A temporary for this permit is being given for one week. Work that needs completed is: cover the cpvc piping in the riser rooms and in the storage closets, provide one hour riser room, provide heat in the riser room, move smoke alarms.

Phone #: ###-#### Inspection requested via web by Andy Thompson
FIRE-Conference8/4/20198/5/20198/5/2019ADONE
DetailsTroy Cobbley
Andy and I discussed boxing in the exposed piping in the closets, filling with insulation but no insulation on the interior wall side. Also the outer layer of sheet rock on the adjoining wall would be cut out to facilitate the transfer of heat from the interior. We also discussed riser room signage and placement of the interior smokd alarms.
call to confirm please! Troy knows what I''m talking about. Phone #: ###-#### Inspection requested via web by Andy Thompson
BLD-Final8/1/20198/1/20198/1/2019PNR
DetailsTell Riley
Please call to schedule Phone #: ###-#### Inspection requested via web by Andy Thompson//need final fire sprinkler inspection, life safety inspection//have plans onsite for final//
BLD-Aging Inspection7/16/20197/16/20197/16/2019 PASS
DetailsTell Riley
recently performed inspection on canopy in park area//dwelling units are still under construction//
BLD-Energy code compliance3/1/20193/4/20193/4/2019APART
DetailsJim Sly
Phone #: ###-#### Inspection requested v OK to rock except areas around bath fans.....2nd floor.........after sprinkler inspection. Talked to Andy about this.
BLD-Framing/Rough-in2/21/20192/21/20192/21/2019PPART
DetailsJim Sly
Phone #: ###-#### Inspection requested via web by Andy Thompson
All OK except....Part on HVAC......Need to verify bath fans are listed....Rated 1hr for ceiling
BLD-Framing/Rough-in2/19/20192/19/20192/20/2019PNR
DetailsJim Sly
Phone #: ###-#### Inspection requested via web by Andy Thompson
BLD-Framing/Rough-in2/16/20192/19/20192/19/2019ANR
DetailsJim Sly
Phone #: ###-#### Inspection requested via web by Andy Thompson
Need Mech R/I
BLD-Conference2/1/20192/1/20192/1/2019PPASS
DetailsJim Sly
Phone #: ###-#### Inspection requested via web by Andy Thompson
BLD-Wall Bracing12/19/201812/19/201812/19/2018PPASS
DetailsJim Sly
Phone #: ###-#### Inspection requested via web by Andy Thompson
BLD-Wall Bracing12/11/201812/12/201812/12/2018PNR
DetailsJim Sly
please call 20-30 min in advance so builder can meet on site. Thank you! Phone #: ###-#### Inspection requested via web by Andy Thompson
Used staples in lieu of nails as shown on approved plan.
BLD-Foundation11/6/201811/6/201811/6/2018PPASS
DetailsJim Sly
Phone #: ###-#### Inspection requested via web by Andy Thompson
BLD-Footing11/4/201811/5/201811/5/2018APASS
DetailsJim Sly
Phone #: ###-#### Inspection requested via web by Andy Thompson