Information based on query as of Thursday, May 16, 2024.
Permit Information
Permit NumberBLD18-03083
StatusFinaled
Name IDAHO PROPERTY MAINTENANCE LLC
Site Address 7855 W EMERALD ST
Project NameGolftec Boise
Customer NumberBLD18-03690
ePlanReviewYes
Description
(2 PERMITS FILED UNDER BLD18-03083 IN EPLANREVIEW)(GOLFTECH) This building is NOT fire sprinklered or alarmed. Permit for tenant improvements to an existing 2,159 sq ft tenant space and to expand 177 sq ft into the adjacent tenant space for a total 2,500 sq ft tenant space. Work to include: demo of existing interior non-bearing walls, sinks, and cabinetry; new non-bearing interior walls and doors, putting green, plumbing for drinking fountain and restroom, new ceiling, new lights and electrical, minor mechanical, and new interior finishes in compliance with Ch. 8 of the 2015 IBC. All work to be done per the approved plans and applicable codes and ordinances. **JAR**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final1/11/20191/11/20191/11/2019PPASS
DetailsMike Jordan
Will Phone #: ###-####. Ok for prm occ.
BLD-Final1/9/20191/9/20191/9/2019PPEND
DetailsBrandon Shaw
Need MECh final...
Temp C. of O. is OK...
FIRE-Final Inspection1/8/20191/9/20191/9/2019APASS
DetailsTroy Cobbley
life safety passed
FIRE-Final Inspection1/4/20191/7/20191/7/2019AFAIL
DetailsJim Page
Could not find city approved drawings, emergency illumination for exit discharge needs to be installed on main entry on the north side as well as desiganted exit on the south side. Fire extinguisher needs to be inspected and tagged as well as lowered to below 48 inches to be code compliant.

Phone #: ###-#### Inspection requested via web by Will Thomason
BLD-Final1/4/20191/7/20191/7/2019PCANC
DetailsMike Jordan
Phone #: ###-#### >> Inspection requested via web by Will Thomason
BLD-Ceiling Grid Inspection12/28/201812/28/201812/28/2018PPASS
DetailsBrandon Shaw
Will Phone #: ###-####
BLD-Framing/Rough-in11/19/201811/20/201811/20/2018APASS
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Will Thomason. Inteior steel stud framed walls only ok.
BLD-Framing/Rough-in11/19/201811/19/201811/19/2018PNR
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Will Thomason. Needs to provide the city approved plans.