BLD-Aging Inspection | 2/14/2020 | 2/14/2020 | 2/19/2020 | | DONE |
Tony Young
|
|
|
|
BLD-Aging Inspection | 2/13/2020 | 2/13/2020 | 2/14/2020 | | DONE |
Tony Young
|
|
|
|
BLD-Final | 9/30/2019 | 10/2/2019 | 10/2/2019 | A | PASS |
Tony Young
|
|
|
Steve Phone #: ###-####
|
FIRE-Final Inspection | 9/30/2019 | 10/1/2019 | 10/1/2019 | P | PASS |
Jim Page
|
|
|
Prevously noted items have been corrected, per IBC definition, the area of work is defined as a platform and not a stage, per the 2015 edition of NFPA 13, platforms do not require sprinklers as long as the items listed under 8.15.6.2 are met, walls and lid of little mech room under the platform have been sheetrocked and taped, this meets the requirements of the mentioned NFPA 13 section. No fire alarm modifications, fire sprinkler inspection is complete, fire extinguihsers are placed with current inspection tags. Final life fire safety inspection for area of work complete.
.Steve Phone #: ###-####
|
BLD-Final | 9/25/2019 | 9/27/2019 | 9/27/2019 | A | CANC |
Tony Young
|
|
|
Steve Phone #: ###-####
|
BLD-Final | 9/26/2019 | 9/26/2019 | 9/26/2019 | P | NR |
Tony Young
|
|
|
Steve Phone #: ###-####
|
FIRE-Final Inspection | 9/25/2019 | 9/26/2019 | 9/26/2019 | A | FAIL |
Jim Page
|
|
|
Provide fire sprinklers under stage area per NFPA, section 8.15.17 or meet the exceptions listed under 8.15.1 of NFPA 13.
Steve Phone #: ###-####
|
BLD-Framing/Rough-in | 7/1/2019 | 7/2/2019 | 7/2/2019 | A | PART |
Tony Young
|
|
|
Steve Phone #: ###-####,, deck sheeting,, work in progress,, ok
|
BLD-Energy code compliance | 6/24/2019 | 6/26/2019 | 6/26/2019 | A | PART |
Tony Young
|
|
|
Steve- dry wall inspection Phone #: ###-####,, ok to re-cover soffit areas,, no changes made
|
BLD-Framing/Rough-in | 6/24/2019 | 6/26/2019 | 6/26/2019 | A | PART |
Tony Young
|
|
|
Steve Phone #: ###-####,, stage frame ok
|
BLD-Conference | 5/15/2019 | 5/16/2019 | 5/16/2019 | P | PART |
Tony Young
|
|
|
Steve-please call with a meet time Phone #: ###-####,, site review,,
|
BLD-Conference | 5/16/2019 | 5/16/2019 | 5/16/2019 | A | PART |
Tony Young
|
|
|
Steve-please call with a meet time Phone #: ###-####,, ?s on stage
|