Permit Information
Permit NumberBLD19-04414
StatusFinaled
Name WRIGHT BROTHERS THE BLDG CO EAGLE
Site Address 121 N 9TH ST Unit: 200
Project NameMountain West Bank - Ste 200
Customer Number 
ePlanReviewYes
Description
(MOUNTAIN WEST BANK – SUITE #200) Permit is to remodel an existing 4,251 sq. ft. office tenant space. Approval is contingent upon adhering to the approved plans on file. Work to include: removal of select interior nonbearing wall, removal of select door/door frame, construction of select interior non-bearing walls, select new door/door frames and interior finishes in compliance with Ch. 8 of the current IBC. This building is fully Fire Sprinklered. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final1/7/20201/8/20201/8/2020PPASS
DetailsDave Hannah
Phone #: 2088694278 >> Inspection requested via mobile web by Ian
FIRE-Final Inspection1/7/20201/8/20201/8/2020PPASS
DetailsJim Page
Previously noted items have been corrected, fire sprinkler inspection is complete, fire aalrm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

Phone #: 2088694278 >> Inspection requested via mobile web by Ian
BLD-Final1/3/20201/6/20201/7/2020PCANC
DetailsDave Hannah
Ian Phone #: ###-####
FIRE-Final Inspection1/6/20201/7/20201/7/2020PFAIL
DetailsJim Page
Provide code compliant door hardware on main lobby door to TI, thumb turn deadbolts are in place, double keyed deadbolts were in place at time of inspection. Provide signage at main lobby door reading "Door to remain unlocked while space is occupied".

Phone #: 2088694278 >> Inspection requested via mobile web by Ian
FIRE-Conference11/22/201911/22/201911/22/2019ADONE
DetailsJim Page
Fire conference is complete, fire aalrm notification will be required in conference room (Room 209 is a conference room, not an office as shown on city approved drawings) and breakroom, a seperate permit is required for any and all fire alarm modifications. Sprinkler heads in main lobby for tenant space are 155 degree heads and are less than 12 inches from heat registers, heads will need to be changed to intermediate temperature sprinkler heads. Fire extinguishers to be mounted in discussed locations.
FIRE-Final Inspection11/21/201911/22/201911/22/2019ACANC
DetailsJim Page
Request was for a conference, not a final inspection, this request is cancelled.

Please call for access- Ian Phone #: ###-####
BLD-Framing/Rough-in11/21/201911/22/201911/22/2019APASS
DetailsDave Hannah
Please call for access- Ian Phone #: ###-####