Permit Information
Permit NumberELE17-03140
StatusFinaled
Name POWER PLUS INC
Site Address 1424 N ORCHARD ST
Project NameThe Masonry Center Showroom Re
Customer NumberS003940
ePlanReviewNo
Description
Alteration: Added four floor boxes
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/18/20199/18/20199/18/2019PPASS
DetailsRock A. Hudson
Duane Oreilly contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Correction made. Final ok
Final9/5/20199/6/20199/6/2019AFAIL
DetailsRock A. Hudson
Duane Oreilly is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
314.25- All boxes shall have covers.
330.30- MN cable shall be secured with in 12" of a box.
Building permit noted some areas of grid being replaced. History of inspections show no grid inspection performed. Just in from front door looked up and noticed 2 open boxes and KO seals needed and unsecured MC cable.
Will need to meet contact on site with ladder to check areas above grid.
ELE-Aging Inspection9/5/20199/5/20199/5/2019 FAIL
DetailsRock A. Hudson
Called left message with contact. I remember job would be done in phases so might be still under construction
Electrical Rough-In1/31/20182/1/20182/1/2018PPASS
DetailsRock A. Hudson
Terry Cushing is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Entry 1/2 wall and drinking fountain wall rough in ok cover
Electrical Rough-In1/23/20181/24/20181/24/2018ACANC
DetailsRock A. Hudson
Terry Cushing is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
Called contact. No new work done yet.
Valuation corrected. Thank You
Electrical Rough-In1/23/20181/23/20181/23/2018PPART
DetailsRock A. Hudson
Terry Cushing is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
Contractor to increase valuation, future inspections may be delayed if not corrected.
Walls noted on contractor print, east office walls, walls with display sconces, south wall near drinking fountain, and fireplace walls and hardlids noted only rough in ok cover
Electrical Rough-In11/16/201711/16/201711/16/2017PFAIL
DetailsRock A. Hudson
Jason Wells is contact on this project at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
NO BLD permit found. Spoke with rep and stated architect still working on plans. Unable to inspect due to BLD permit issue. 330.30- MC shall be secured with in 12" of a box.
362.30- ENT shall be secured with in 3' of a box.
Verbal with contact
Electrical Rough-In9/20/20179/21/20179/21/2017APASS
DetailsRock A. Hudson
Terry Cushing is the contact on site ###-#### Phone #: ###-#### Inspection requested via web by Debby Pierce
Future work to be permited when building permit is pulled.
Floor receptacles only rough in ok cover