Permit Information
Permit NumberELE18-00727
StatusFinaled
Name PRIORITY ELECTRIC
Site Address 1150 W MYRTLE ST
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Ground up building. All required lighting, gear, site, and branch electrical.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/9/20187/10/20187/10/2018APASS
DetailsRock A. Hudson
Justin Johnston...###-#### Phone #: ###-#### Inspection requested via web by Tom Jenkins Final ok
Final7/6/20187/6/20187/6/2018PPART
DetailsRock A. Hudson
Temp final for training inspection. Please make it later in the afternoon after 3 if possible or if necessary. Phone #: ###-#### Inspection requested via web by Tom Jenkins
All GFCI protection in place an tested OK. Signed TCO line on card.
Conference7/5/20187/6/20187/6/2018ADONE
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tom Jenkins
Discussed and double checked all requirement for temp occupancy. All 1,2,3 pole receptacles shall have GFCI protection or be hard wired with disconnecting means installed. If this cannot be accomplished all power to the receptacles for the appliances needing GFCI protection shall be diconnected or be locked out so appliance cannot be used until code compliant.
Final7/3/20187/3/20187/3/2018PCANC
DetailsRock A. Hudson
Temp final Phone #: ###-#### >> Inspection requested via web by Tom Jenkins Inspection cancelled from web by: Tom Jenkins
Final7/2/20187/3/20187/3/2018AFAIL
DetailsRock A. Hudson
Temp final Phone #: ###-#### Inspection requested via web by Tom Jenkins
210.8(B)- Other Than Dwelling Units. All single-phase receptacles rated 150 volts to ground or less, 50 amperes or less and threephase receptacles rated 150 volts to ground or less, 100 amperes or less installed in the following locations shall have ground-fault circuit-interrupter protection for personnel.
Multilple in kitchen area.
Electrical Rough-In7/2/20187/2/20187/2/2018PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tom Jenkins
North underground under sidewalk for lights
Electrical Rough-In6/30/20186/30/20186/30/2018PPASS
DetailsRock A. Hudson
Ceiling ###-####.
Boarder tiles removed, Thak you.
Grid rough in ok cover
Electrical Rough-In6/29/20186/29/20186/29/2018PFAIL
DetailsRock A. Hudson
Ceiling cover. Thank you Phone #: ###-#### Inspection requested via web by Tom Jenkins
BCC 4 05 17- It shall be unlawful to cover electrical wiring prior to inspection. Grid boarders remove and recall
Permanent Service6/25/20186/26/20186/26/2018PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tom Jenkins
p/s u/g n ok
Electrical Rough-In6/19/20186/20/20186/20/2018APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tom Jenkins
Underground west side to light and sign locations rough in ok cover.
Electrical Rough-In6/14/20186/14/20186/14/2018PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tom Jenkins
Menu board bases rough in ok cover
Electrical Rough-In6/11/20186/12/20186/12/2018APASS
DetailsRock A. Hudson
Pole bases Phone #: ###-#### Inspection requested via web by Tom Jenkins
Pole bases rough in ok cover
Electrical Rough-In5/31/20185/31/20185/31/2018PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tom Jenkins
Out front soffit ceiling rough in ok cover
Electrical Rough-In5/16/20185/17/20185/17/2018PPASS
DetailsJames Ady
Ceiling Cover Phone #: ###-#### Inspection requested via web by Tom Jenkins cans had not been wired but, all j box covers were in place at time of inspection hard lid areas only ok to cover
Electrical Rough-In5/8/20185/9/20185/9/2018PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tom Jenkins
All walls complete wall rough in ok cover
Electrical Rough-In5/2/20185/3/20185/3/2018APART
DetailsRock A. Hudson
Wall inspections Phone #: ###-#### Inspection requested via web by Tom Jenkins
Bread room, serving window area, back house, bathroom walls noted rough in ok cover
Electrical Rough-In4/27/20184/27/20184/27/2018PPASS
DetailsRock A. Hudson
Exterior wall inspection. Phone #: ###-#### Inspection requested via web by Tom Jenkins
Exterior walls only rough in ok cover
Conference3/19/20183/19/20183/19/2018PFAIL
DetailsRock A. Hudson
110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal
circuit voltage at least equal to the current that is available at the line terminals of the equipment. Equipment intended to interrupt current at other than fault levels shall have an interrupting rating at nominal circuit voltage at least equal to the current that must be interrupted.
NEC 110.10- Circuit Impedance, Short-Circuit Current Ratings, and Other Characteristics. The overcurrent protective devices, the
total impedance, the equipment short-circuit current ratings, and other characteristics of the circuit to be protected shall be selected and coordinated to permit the circuit protective devices used to clear a fault to do so without extensive damage to
the electrical equipment of the circuit. This fault shall beassumed to be either between two or more of the circuit conductors or between any circuit conductor and the equipment grounding conductor(s) permitted in 250.118. Listed equipment applied in accordance with their listing shall be considered to meet the requirements of this section.
On 3-12-18 checked available short circuit current off service located on property to sub-gear at structure being built using Eaton FC2 available fault current calculator. Available fault current at main disconnecting means, 62,561 amps, 75' to building equipment, 2 parallel runs of 600 kcmil copper conductors. App states total available short circuit current at building equipment is 36,867 amps and 10k rated branch circuit overcurrent devices.
Please submit back to engineer for correction. Must see documentation of correction of available short circuit values.
Electrical Rough-In3/12/20183/12/20183/12/2018PPASS
DetailsRock A. Hudson
Slab inspection. Early afternoon if possible. Thank you Phone #: ###-#### Inspection requested via web by Tom Jenkins
Under slab rough in ok cover
Electrical Rough-In3/8/20183/8/20183/8/2018PPASS
DetailsRock A. Hudson
Underground inspection Phone #: ###-#### Inspection requested via web by Tom Jenkins
Feeder underground conduits rough in ok cover
Conference2/28/20183/7/20183/6/2018ADONE
DetailsRock A. Hudson
Verify 30 amp receptacle in spider box and other have GFCI protection at ploe or at spider box. If GFCI is absent order cord to be removed forn temp power suppy.
pole checked on 3-2-18 ok
Electrical Rough-In3/2/20183/2/20183/2/2018PPASS
DetailsEric Story
Check 30 amp at spider box for GFCI protection ###-####
GFCI protection fixed in temp power
Electrical Rough-In2/27/20182/28/20182/28/2018PPASS
DetailsRock A. Hudson
Ufer Phone #: ###-#### Inspection requested via web by Tom Jenkins
Concrete encased electrode rough in ok cover
Electrical Rough-In2/28/20182/28/20182/28/2018PFAIL
DetailsRock A. Hudson
Ufer Phone #: ###-#### Inspection requested via web by Tom Jenkins
590.6(B)- Receptacles other than 120 volt used for temp power shall have GFCI protection. 30 amp spider box.
Electrical Rough-In2/27/20182/27/20182/27/2018PPASS
DetailsRock A. Hudson
Sleeves under footing forms. Phone #: ###-#### Inspection requested via web by Tom Jenkins
Check temp power to spider box 30 amp receptacle on spider box no GFCI prtection. Underground as noted rough in ok cover
Electrical Rough-In3/2/20183/2/2018 P 
DetailsJim Little
Correction made to temp power pole. Thank you Phone #: ###-#### >> Inspection requested via web by Tom Jenkins