Final | 4/29/2019 | 4/29/2019 | 4/29/2019 | P | PASS |
Eric Story
|
|
|
Mark Phone #: ###-#### Card on site final ok
|
Final | 4/24/2019 | 4/25/2019 | 4/25/2019 | A | PART |
James Ady
|
|
|
Mark Phone #: ###-#### 110.26D Illumination in panel board rooms shall not be controled by automatic means. 210.8 Where required by 210.8 A through E, the GFCI shall be readily accessible (See definition of readily accessible. Xmas recep.) 210.8B5. Receps within 6ft of sink shall be GFCI protected.(Fitness room) Hall receps and courtyard GFCI in area C not working.
|
Final | 4/10/2019 | 4/11/2019 | 4/11/2019 | A | PART |
James Ady
|
|
|
Mark- final inspection for wing "A" Phone #: ###-#### Partial final "A"wing (West side of entry) OK
|
Electrical Rough-In | 4/1/2019 | 4/2/2019 | 4/2/2019 | A | PASS |
James Ady
|
|
|
reinspection // Mark Phone #: ###-#### Remaining areas of drop ceiling ok to cover
|
Electrical Rough-In | 3/29/2019 | 4/1/2019 | 4/1/2019 | A | PASS |
James Ady
|
|
|
celing- Mark Phone #: ###-#### Drop ceilings only. Salon and restrooms not ready at this time. MC ok to be supported by grid wire as per D. Degrang.
|
Electrical Rough-In | 2/26/2019 | 2/26/2019 | 2/26/2019 | P | PASS |
James Ady
|
|
|
Mark Phone #: ###-#### Half wall in kitchen area only ok to cover
|
Electrical Rough-In | 2/25/2019 | 2/25/2019 | 2/25/2019 | P | PASS |
James Ady
|
|
|
would like as early as possible Phone #: ###-#### Front desk half wall and soffit ok to cover
|
Electrical Rough-In | 2/21/2019 | 2/21/2019 | 2/21/2019 | P | PASS |
James Ady
|
|
|
Late afternoon // Mark Phone #: ###-#### Remaining ceiling and front entry columns only ok to cover
|
Electrical Rough-In | 2/14/2019 | 2/15/2019 | 2/15/2019 | A | PASS |
James Ady
|
|
|
Mark Phone #: ###-#### Drop ceiling areas in cooridors ok to cover
|
Electrical Rough-In | 1/22/2019 | 1/22/2019 | 1/22/2019 | P | PASS |
James Ady
|
|
|
Mark Phone #: ###-#### Remaining area ok to cover
|
Electrical Rough-In | 1/16/2019 | 1/16/2019 | 1/16/2019 | P | PART |
James Ady
|
|
|
Mark-would like as late as poss if poss Phone #: ###-#### Exterior walls only. Hard lids only. No interior walls at this time Area c only
|
Electrical Rough-In | 1/11/2019 | 1/11/2019 | 1/11/2019 | P | PASS |
James Ady
|
|
|
Mark Phone #: ###-#### Fornt canopy and back patio ok to cover
|
Electrical Rough-In | 12/28/2018 | 12/28/2018 | 12/28/2018 | P | PASS |
James Ady
|
|
|
Mark Phone #: ###-#### area c only ok to cover
|
Electrical Rough-In | 12/3/2018 | 12/3/2018 | 12/3/2018 | P | PASS |
James Ady
|
|
|
Area D r/i - Mark Phone #: ###-#### area D only ok to cover
|
Rough-In Permanent Service | 11/9/2018 | 11/13/2018 | 11/13/2018 | A | PASS |
James Ady
|
|
|
Mark Phone #: ###-#### Hard lids in Bathrooms only p/s u/g n ok
|
Electrical Rough-In | 10/26/2018 | 10/29/2018 | 10/29/2018 | A | PASS |
James Ady
|
|
|
Mark Phone #: ###-#### Do not cover ceilings in Bathrooms. Walls only. Rooms ok to cover walls and ceilings. Area "A" only
|
Electrical Rough-In | 10/12/2018 | 10/15/2018 | 10/15/2018 | A | PASS |
James Ady
|
|
|
Underground - Mark Phone #: ###-#### Underground for 3 parking lot lights along front of lot ok to cover
|