Final | 5/15/2019 | 5/16/2019 | 5/16/2019 | A | PASS |
Rock A. Hudson
|
|
|
The lock code is 9102. Please call Marcus Stevens with any questions ###-####. Phone #: ###-#### Inspection requested via web by Jeremy Cloud Final ok
|
Permanent Service | 3/5/2019 | 3/5/2019 | 3/5/2019 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Jeremy Cloud p/s u/g n ok
|
Permanent Service | 2/11/2019 | 2/11/2019 | 2/11/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Inspect parking lot service to energize. Phone #: ###-#### Inspection requested via web by Jeremy Cloud 110.24- Available fault current shall be posted prior to permanent service inspection with value and date calculated. 250.142- Grounded circuit conductor shall be allowed to ground non-current carrying metal parts of an enclosure of a service disconnecting means. Grounded conductor is bonded in CT can. Equipment ground through raceway is a parallel path to the grounded conductor. Remove equipment ground from CT can to service disconnecting means.
|
Electrical Rough-In | 1/15/2019 | 1/16/2019 | 1/16/2019 | P | PASS |
Rock A. Hudson
|
|
|
Inspect underground conduit and light pole bases for cover. Phone #: ###-#### Inspection requested via web by Jeremy Cloud As noted rough in ok cover
|
Electrical Rough-In | 1/11/2019 | 1/14/2019 | 1/14/2019 | A | PASS |
Rock A. Hudson
|
|
|
Inspect underground conduit for cover. Phone #: ###-#### Inspection requested via web by Jeremy Cloud Underground to pole bases rough in ok cover
|