Final | 7/26/2019 | 7/26/2019 | 7/26/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack General contractor foreman stated could not find sign off card when asked. No card posted. Final ok
|
Final | 7/25/2019 | 7/25/2019 | 7/25/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Final for pad 3 Phone #: ###-#### Inspection requested via web by Lee VanSchoiack 314.25- All boxes shall have covers. 3 located in ceiling above panel, 1 ceiling south side. 330.30- MC cable shall be secured with in 12" of a box. Several thru out. 590.6- All 15 and 20 amp 120 volt receptacle outlets installed for power during construction shall have GFCI protection for personel.
|
Electrical Rough-In | 7/16/2019 | 7/17/2019 | 7/16/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack East underground for 6 lights rough in ok cover
|
Electrical Rough-In | 7/11/2019 | 7/11/2019 | 7/11/2019 | A | PASS |
Rock A. Hudson
|
|
|
exterior canopies Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Areas noted rough in ok cover
|
Permanent Service | 5/31/2019 | 6/3/2019 | 6/3/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack p/s u/g n ok
|
Electrical Rough-In | 5/23/2019 | 5/24/2019 | 5/24/2019 | A | PASS |
Rock A. Hudson
|
|
|
walls Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Perimeter shell walls rough in ok cover
|
Electrical Rough-In | 5/23/2019 | 5/23/2019 | 5/23/2019 | P | CANC |
Rock A. Hudson
|
|
|
Walls Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack Inspection cancelled from web by: Lee VanSchoiack
|
Electrical Rough-In | 4/4/2019 | 4/4/2019 | 4/4/2019 | A | PASS |
Rock A. Hudson
|
|
|
ug conduit Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Underslab rough in ok cover
|
Electrical Rough-In | 3/27/2019 | 3/27/2019 | 3/27/2019 | A | PASS |
Rock A. Hudson
|
|
|
ufer Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Concrete encased electrode rough in ok cover
|