Final | 9/17/2019 | 9/17/2019 | 9/17/2019 | A | PASS |
Mark Moncarr
|
|
|
I need to run my kids to school at 9am and have a doctor''s appointment at 9:30. If it works before then, great. If not, can we reschedule. Phone #: ###-#### Inspection requested via web by Nick Smith Ok final. 50a brkr changed to 60a for garage, panel labeled.
|
Electrical Rough-In | 9/10/2019 | 9/10/2019 | 9/10/2019 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Nick Smith Discussed GFCI protection, Tamper resistant, NM supports not to exceed 4 1/2', 60 amp minimum feed to garage with more than 2 circuits. Wiring ran on surface of upper plates and down side of studs to boxes. Explained all below 8' needs guard strips to protect from physical damage. Rough in ok.
|
Conference | 8/5/2019 | 8/5/2019 | 8/5/2019 | A | PASS |
Mark Moncarr
|
|
|
Trench is dug with conduit. I''d like to bury it but want the sign off first. Phone #: ###-#### Inspection requested via web by Nick Smith Ok cover trench from house to detached garage. 20"-24" deep.
|
Conference | 7/5/2019 | 7/8/2019 | 7/8/2019 | A | DONE |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Nick Smith Discussed new power to garage, and the required circuits a long with protection.
|