Final | 8/24/2019 | 8/26/2019 | 8/26/2019 | A | PASS |
Rock A. Hudson
|
|
|
Corrections have been made since last inspection. Phone #: ###-#### Inspection requested via web by Dan Hilke Final ok
|
Final | 8/17/2019 | 8/19/2019 | 8/19/2019 | A | FAIL |
Tom Saunders
|
|
|
Homeowner said he would be there. Trench is still open, and wiring inside is not going to get covered. GFCI Bkr in meterbox, #12 THHN in conduit to shed, and 12-2 MC inside with metal boxes that have gnd pigtails. Give me a call if there''s any questions. Phone #: ###-#### Inspection requested via web by Dan Hilke... 1..accessory building shall have luminaire on exterior...210.70(2)(2) 2..disconnect needs installed...225.31
|
Electrical Rough-In | 8/19/2019 | 8/19/2019 | 8/19/2019 | A | PASS |
Tom Saunders
|
|
|
Homeowner said he would be there. Trench is still open, and wiring inside is not going to get covered. GFCI Bkr in meterbox, #12 THHN in conduit to shed, and 12-2 MC inside with metal boxes that have gnd pigtails. Give me a call if there''s any questions. Phone #: ###-#### Inspection requested via web by Dan Hilke.... trench ok to cover interior rough in ok
|