Final | 10/25/2019 | 10/28/2019 | 10/28/2019 | A | PASS |
Tom Saunders
|
|
|
Call Luke ###-#### on your way and with any questions please. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan... corrections made-circuit directory and neutral seperation
connected load re-engineered by engineer to show full connected load of existing business and new appliances-meets requirements...future loads added by neighboring business will need addressed at that time...ID Power is aware of issue
|
Final | 10/23/2019 | 10/24/2019 | 10/24/2019 | A | FAIL |
Rock A. Hudson
|
|
|
There will people there. If you have any questions please feel free to contact Fred ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan A 200 amp disconnect has been installed to replace a 100 amp disconnect. Change out was completed after hours and reconnected by electrical contractor. 215.2- Feeders shall be sized as per load calculation in parts III, IV, V of artical 220. As per engineer drawing feeders shall be sized to carry 786 amps. 600 KCMIL aluminum installed rated at 340 amps. Feeder in question feeds 2 150amp disconnects and the 200 amp disconnect. Additional 100 amp taps out of main disconnecting means. 250.24(A)(5)- The grounded conductor shall not be connected to non-current carrying metal parts on load side of service disconnecting means. 408-4- Circuit directory shall be complete.
|
Electrical Rough-In | 9/23/2019 | 9/24/2019 | 9/24/2019 | A | PASS |
Rock A. Hudson
|
|
|
Call Luke with any questions at ###-#### Phone #: ###-#### Inspection requested via web by Clayton Morgan Hardlids rough in ok cover
|
Electrical Rough-In | 9/20/2019 | 9/20/2019 | 9/20/2019 | P | PASS |
Rock A. Hudson
|
|
|
There will be someone there. If you have any questions please feel free to contact Luke ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Missing exhaust fan in bath. Walls only rough in ok cover
|
Electrical Rough-In | 9/18/2019 | 9/19/2019 | 9/19/2019 | A | PART |
Rock A. Hudson
|
|
|
There will be someone there. If you have any questions please feel free to contact Fred ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Kitchen area only rough in ok cover
|