Permit NumberELE19-03215
StatusFinaled
Name ENERGY ENTERPRISE GROUP LLC
Site Address 1290 W MYRTLE ST Unit: 190
Project Name 
Customer Number774
ePlanReviewNo
Description
Alteration: Electrical for TI
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/24/201910/25/201910/25/2019APASS
DetailsRock A. Hudson
our site contact is Sam. 30 minute call ahead is appreciated Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Final ok
Final10/17/201910/17/201910/17/2019PPART
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
210.8(B)- All single phase receptacles up to 50 amp located with in 6' of a sink shall have GFCI protection. Dryer receptacle.
300.11- All cables shall not be supported by grid. Bicycle room LV cables added after ceiling inspection.
330.12- Exposed MC cable installed where subject to physical damage shall be protected from damage. Patches in laundry and S.W. room and reception.
330.30- Support MC in laundry ceiling.
TCO ok for moving in equipment only. Washer and dryer receptacles shall remain accessible.
Electrical Rough-In10/10/201910/10/201910/10/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Grid for 3 offices, bike room, corridor rough in ok cover.
Final10/3/201910/4/201910/4/2019ACANC
DetailsJames Ady
Please call 30 mins prior. Phone #: ###-#### Inspection requested via web by Kerri Hamilton Called in wrong permit
Electrical Rough-In10/2/201910/2/201910/2/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Boarders only for grid in west room only ok cover.
Electrical Rough-In9/10/20199/11/20199/11/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Bathroom hardlids rough in ok cover
Electrical Rough-In9/5/20199/5/20199/5/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Bathroom walls rough in ok cover
Electrical Rough-In9/3/20199/4/20199/4/2019ACANC
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Not all wiring shown on print are present in walls. Recall when ready
Electrical Rough-In8/27/20198/27/20198/27/2019PPART
DetailsRock A. Hudson
Please call 30 mins prior Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Warned not to cover in ant way prior to inspection.
All bathroom walls not ready, rest of walls rough in ok cover