Final | 12/6/2019 | 12/6/2019 | 12/6/2019 | P | PASS |
Tom Saunders
|
|
|
Ryan Phone #: ###-####...panel complete and rewire of damaged wall..ok to final
|
Rough-In Permanent Service | 11/6/2019 | 11/7/2019 | 11/7/2019 | A | PASS |
Tom Saunders
|
|
|
code 4810 Phone #: ###-#### Inspection requested via web by Ryan Wake... minimum corrections made to get service turned back on and cover rough-in of new walls other corrections need addressed by final rough ok to cover p/s o/h reconnect ok
|
Rough-In Permanent Service | 11/5/2019 | 11/6/2019 | 11/6/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Unoccupied. Lock box on back door code 4810 Phone #: ###-#### Inspection requested via web by Ryan Wake 250.53(A)(2)- Unable to verify supplemental ground rod, covered by pavers. 300.4- nail plates needed in bedroom north west corner. BCC 4-05-32- No code violation to be retained. Existing NM cables run through short pieces of PVC with ends open with exposed NM cable. 334.12- NM cable shall not be installed outdoors or tun in exterior conduits, wet or damp locations. NM cable shall not be installed where subject to physical damage, back patio, carport, inside of back door.
|