Name SHILO AUTOMATIC SPRINKLER CO
Site Address 951 E FRONT ST
Project Name916 PARK APPARTMENTS
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of protecting a (4) level apartment building. There is a Class I manual wet standpipe in two stairwells. There are live/work units protected as light hazard. Residential sprinklers are being used extensively. The majority of the piping will be CPVC.

Plan Mod #1 – 10/02/2014
Rerouted piping in stair #2

The 6” underground was installed under permit FIR14-00103

916 Park Apartments - To construct a new 70,965 square foot, four story, wood framed apartment building with some first floor retail shell areas for future tenants. This permit also includes related site improvements. The first floor includes 3,940 sq. ft. of retail areas, a 395 sq. ft. Gym, 2,255 sq. ft. of storage areas, a 210 sq. ft. office area, along with (7) Live/work Units, and (8) one bedroom apartments. The second through fourth floors consist of a mix of one and two bedroom apartments. There are a total of 68 apartments in this building. . First Floor: 19,145 sq. ft., Second Floor: 17,470 sq. ft., Third Floor: 17,175 sq. ft., Fourth Floor 17,175 sq. ft. The building is fully fire sprinkled and the sprinklers are used for area and story increases. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/16/20151/16/20151/16/2015PPASS
DetailsForrest France
Correction items finished. Final walkthrough passed.
INSP-Final Inspection1/8/20151/8/20151/8/2015PNR
DetailsForrest France
Items noted include; missing sprinkler at the north stairway top level, replace painted sprinkler, certify DCVA, missing caps at the FDC, secure control valve to rooftop hose connection, replace missing flow switch covers, install missing escutcheon at electrical room.
INSP-Final Inspection12/30/20141/6/20151/6/2015PPART
DetailsForrest France
INSP-Sprinkler Rough-in12/19/201412/22/201412/22/2014PPART
DetailsForrest France
OH work at the 1st, 2nd, 3rd and 4th floor corridors approved for cover. Need to provide vertical restraint at one armover and pendent 4th floor north end.
INSP-Conference12/12/201412/15/201412/15/2014APART
DetailsForrest France
Okay to cover fire sprinkler work at the 1st floor center corridor sheetrock lid ceiling. Discussed coverage at the 2nd, 3rd, and 4th floor mechanical rooms adjacent to the elevator equipment rooms.
INSP-Conference12/12/201412/15/201412/12/2014ACANC
DetailsForrest France
Ken is your contact. Please call 1/2 hour before inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Conference11/18/201411/19/201411/19/2014ADONE
DetailsForrest France
On site conference with general contractor regarding NFPA 13R 6.4.6.3.2.1, (2.2),(2.3) and table 6.4.6.3.4.2
INSP-Conference11/18/201411/18/201411/18/2014PDONE
DetailsForrest France
Regarding obstructions to sprinkler coverage.
INSP-Sprinkler Rough-in11/12/201411/13/201411/13/2014APART
DetailsForrest France
Coverage at units where sprinklers are adjacent to surface mounted light fixtures to meet NFPA 13D 6.4.6.3.2.1, 6.4.6.3.2.2, 6.4.6.3.2.3.
INSP-Sprinkler Rough-in11/12/201411/12/201411/13/2014PPART
DetailsForrest France
OH fire sprinkler work at three restrooms 1st floor south okay for cover. Coverage at soffit SE corner also approved for cover.
INSP-Sprinkler Rough-in9/25/20149/26/20149/26/2014APART
DetailsForrest France
Verified drops to pendent heads at 1st floor east side unit restrooms for sheetrock ceilings, eight locations. Need to fire stop at upper lid as discussed.
INSP-Sprinkler Rough-in9/9/20149/9/20149/9/2014APART
DetailsForrest France
Need to provide a plan modification for resubmittal due to field changes in pipe routing, coverage at the stairways and landings prior to permit final.
INSP-Sprinkler Rough-in/Hydro9/2/20149/3/20149/3/2014APART
DetailsForrest France
OH hydrostatic testing for the 1st thru 4th floors including the standpipe completed acceptable.
INSP-Sprinkler Rough-in8/28/20148/29/20148/29/2014APART
DetailsForrest France
INSP-Sprinkler Rough-in8/27/20148/28/20148/28/2014PPART
DetailsForrest France
OH rough-in at 4th floor units. Noted exposed CPVC at the electrical/mechanical closet.
INSP-Sprinkler Rough-in8/22/20148/25/20148/25/2014APART
DetailsForrest France
Completed rough-in inspection for the third floor level apartment units. One missing head added while on site, upright at the mech/electrical closet okayed, need to relocate branchline at the SE unit away from metal edge at beam. Expansion joint needs finished. Plan mod required for changes to sprinkler coverage at the stairways all levels.
INSP-Sprinkler Rough-in/Hydro8/19/20148/19/20148/19/2014APART
DetailsForrest France
Inspection for standpipe completed. Need to provide seismic clearance at floor landings, install guage at the top level.
INSP-Sprinkler Rough-in8/11/20148/12/20148/19/2014PPART
DetailsForrest France
OH rough-in at the second floor completed. Need to provide flushing cap at the south end main per plan note. Locations of sprinklers to meet obstruction criteria per NFPA 13 with regard to light fixtures and ceiling fans as discussed.
INSP-Sprinkler Rough-in8/8/20148/8/20148/8/2014APART
DetailsForrest France
Rough-in at 1st floor as noted
INSP-Sprinkler Rough-in8/6/20148/7/20148/7/2014APART
DetailsForrest France
Rough-in inspection for the 1st floor retail and live work units completed. Combustible concealed spaces to be sprinklered or meet NFPA 13 exceptions.