Permit Information
Permit NumberFIR18-00129
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 3321 N COLE RD
Project NameCSL Plasma TI
Customer Number 
ePlanReviewYes
Description
[CSL Plasma]
The fire sprinkler scope of work consists of adding, plugging and relocating sprinklers to accommodate new wall and ceiling configuration. A new double interlock preaction system is being added to the freezers.

[BLD17-04479]
The fire sprinkler system is used for building area increase and for fire area. Interior nonstructural demolition work was done under permit BLD18-00076. To completely renovate a 11,653 square foot tenant space for a blood plasma collection facility where no one will be incapable of self-preservation. Work is to include a 400 square foot recessed concrete slab on grade to accommodate the floor thickness of a new walk-in freezer; concrete floor patches at plumbing trenches; concrete footings, steel columns, and a steel beam to redirect roof gravity loads where a column will be removed; structural upgrades to the roof structure to support new roof top HVAC units; exterior concrete landings, ramps, rails, and awnings at the back exterior doors; new concrete stem walls where existing exterior doors will be removed in the storefront; interior nonbearing walls; suspended acoustical ceilings; gypsum board soffits and bulkheads; 2 multi-user toilet rooms accessible to the disabled for the public; 2 multi-user toilet rooms accessible to the disabled for employees; interior windows; interior doors; double-acting gates; service counters; new storefront doors and windows; millwork; equipment; furniture, and interior finishes. Special Inspection is required for soils, concrete, masonry, welding, and epoxy anchors and other anchors post-installed in hardened concrete. The West awnings are allowed to be deferred submittal items. The work is required to comply with the approved drawings, with the structural design, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 (including quick-response heads installed in light-hazard areas) and the partial fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**

Alternative Materials and Methods:

• There are no AMM at this time.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/7/20186/8/20186/7/2018APASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro6/4/20186/6/20186/6/2018APASS
DetailsTroy Cobbley
Permit finaled


Contact Andrew Larson ###-#### 30 min. prior to 24 hr hydro test start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in/Hydro6/1/20186/5/20186/5/2018APART
DetailsTroy Cobbley
The 200lb overhead hydro for the pre-action system passed. The 24 hour air test was started at 9:30 with 45psi on the guage.


Contact Andrew Larson ###-#### 30 min prior to Hydro 24 hr Test start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in/Hydro6/1/20186/4/20186/4/2018ACANC
DetailsTroy Cobbley
Rescheduled for tomorrow morning.

Contact Andrew Larson ###-#### 30 min prior to Hydro Test start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Final Inspection5/29/20186/1/20186/1/2018PFAIL
DetailsTroy Cobbley
Need 200lb test and 24 hour air test and the interconnects with the fire alarm panel tested.

Contact Anrew Larson - ###-#### 30 Min prior to Fire Final Insp Start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in5/23/20185/24/20185/24/2018PPASS
DetailsTroy Cobbley
The previous corrections have been made. Piping can be covered. There are no fire review comments on site. I will need these prior to a final sign off and all conditions, if any, will need to be met.

ontact Andrew Larson ###-#### 30 min prior to RTC Insp Start please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in5/22/20185/23/20185/23/2018PPART
DetailsTroy Cobbley
Piping is ok to cover. I noted one pendant needs to be relocated near the front of the building and heads need to be added/relocated in two storage areas. I will check these heads at next inspection but piping can be covered.

Contact Andrew Larson - ###-#### 30 min prior to RTC Insp Start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in5/1/20185/4/20185/4/2018APASS
DetailsTroy Cobbley
Todays inspection was to verify hanger and earth quake bracing attachments so that the insulation backing can be installed. Not all areas had been completed so another inspection will be needed.
INSP-Sprinkler Rough-in4/2/20184/2/20184/2/2018PCANC
DetailsTroy Cobbley
Contact Hunter Anderson ###-#### 30 min prior to Partial RTC Insp start please Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
INSP-Conference3/19/20183/19/20183/19/2018PDONE
DetailsTroy Cobbley
Leroy and I discussed the hangers. Per Scott Arellano the hangers need to meet code, whether it be current or the code under which they were originally installed.
INSP-Conference3/16/20183/16/20183/16/2018PCANC
DetailsTroy Cobbley
Contact Leroy Anderson ###-#### 30 Min prior to Consult start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank