Permit Information
Permit NumberFIR18-00301
StatusFinaled
Name TRIBAL FIRE SYSTEMS
Site Address 8000 S FEDERAL WAY
Project NameMicron BLDG 39 - UPW AREA
Customer Number 
ePlanReviewYes
Description
[Micron Building 39 CUP - C29420]
The fire sprinkler scope of work consists of a new wet system. The system protects UPW Area pretreatment area and equipment platform

• The underground is under permit FIR17-00502
• See FIR17-00042, FIR18-00001, FIR18-00302 for other permits on this building.
• See addendum for graphic scope of work

Owner's Note:
Occupancy is NOT permitted until the bulk main is protected by fire protection.
[BLD17-01950]
The CUP 3 building (B39) will be located south of the new B51 R&D Expansion Project. This permit is for structural only for building and utility trestle footings, foundations and structural steel components of the total design. The proposed new CUP B39 is 68,000 square feet with a 9,319 sq. ft. equipment platform and is type IIB construction. Building occupancy groups consist of F1, H3, and H4. All work per the approved plans and attached engineering. Special inspections are required. This building is fully fire sprinklered for area increase. CDM

Alternative Materials and Methods:

• There are no AMM at this time
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/15/20197/15/20197/15/2019PPASS
DetailsJim Page
Final fire sprinkler inspection for area of work complete.

Jessica Phone #: ###-####
INSP-Final Inspection6/25/20196/25/20196/25/2019PCANC
DetailsJim Page
No inspection performed for this permit due to time constraints, this request is cancelled per conversation with point of contact.

Please call Dillion Barresi with Stock Construcion Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Final Inspection6/18/20196/19/20196/19/2019ACANC
DetailsJim Page
Inspection request cancelled per conversation with point of contact, city approved drawings/small documents could not be located, city approved drawings and small documents are required for inspection.

Dillion Phone #: ###-####
INSP-Final Inspection4/12/20194/12/20194/12/2019PFAIL
DetailsJim Page
Last inspection performed was on 1NOV2018 which resulted in a fail, no follow inspection has been requested for defecincies noted.

Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Final Inspection10/29/201810/31/201811/1/2018PFAIL
DetailsJim Page
Provide heads under elevated grated platforms that are missing in areas discussed. Provide head gaurds with baffle in areas that are missing. Correct over spaced heads in areas discussed. Provide heads under boilers and chillers as discussed or provide documentation that is approved by the fire code official allowing the coverage to be deleted. Re-install fire sprinklers under elevated obstructions that was removed for obstruction repair. Re-pipe fire sprinkler heads that are blocked by overehead pipe bracing that obscures spray pattern development. Provide fire sprinkler coverage under obstructions next to roll up doors that exceeds the 48inch measurement.

Submit as-builts to Fire sprinkler Plan Reviewer Tim Frost showing all additions of fire sprinklers and the removal of sway bracing due to Type B soil. Provide fire sprinklers onder combined obstructions in areas as discussed. Verify with general contractor to discuss any other punch list items associated with the walkthorugh from this inspection.

1:00 PM inspection would be preferred. Phone #: ###-#### Inspection requested via web by Chris Gregory
INSP-Final Inspection7/30/20187/31/20187/31/2018PPART
DetailsJim Page
Final fire sprinkler inspection complete, fire sprinkler permit will remain in issued status until project is complete due to possible obstructions needing coverage.

Chris Phone #: ###-####y
INSP-Sprinkler Rough-in/Hydro6/15/20186/18/20186/18/2018PDONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauge.

Chris Phone #: ###-####Chris Phone #: ###-####