INSP-Final Inspection | 1/31/2019 | 2/1/2019 | 2/1/2019 | A | PASS |
Jim Page
|
|
|
Final inspection for clean agent system complete.
On Site Tech Jeremy Egbert - ###-#### Inspection requested via web by Eric Stanley
|
INSP-Sprinkler Rough-in/Hydro | 1/23/2019 | 1/28/2019 | 1/28/2019 | A | FAIL |
Jim Page
|
|
|
Smoke detectors in server room are to close to HVAC registers, need a minimum of 36 inshes from air flow edge to smoke detectors. Verify allowed clearance around nozzles as well as distance from wall.
.
Jeremy Phone #: ###-####
|