INSP-Final Inspection | 1/1/2019 | 1/2/2019 | 1/2/2019 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Ken Webster
|
INSP-Final Inspection | 12/27/2018 | 12/28/2018 | 12/28/2018 | A | FAIL |
Troy Cobbley
|
|
|
Need as-builts/plan mods for all of the candella changes, need to discuss Entry way notification with plan review and add if required, need weather proof backbox in Dishwashing area on the speaker strobe, need to verify phone lines, need to verify equipment and batteries, need to verify dedicated circuit, need to verify function of notification.
Ken Phone #: ###-####
|
INSP-Alarm Testing | 12/17/2018 | 12/18/2018 | 12/18/2018 | A | DONE |
Troy Cobbley
|
|
|
The testing of the fire smoke dampers performed today. One is no-functional and will need to be re-tested.
Buck-partial Phone #: ###-####
|
INSP-Alarm Testing | 12/13/2018 | 12/14/2018 | 12/14/2018 | A | DONE |
Troy Cobbley
|
|
|
Today we tested the second duct smoke detector that failed to work yesterday. Today it functioned correctly.
inspecting in -ducts in Pioneer gym Phone #: ###-#### Inspection requested via web by Ken Webster
|
INSP-Alarm Testing | 12/12/2018 | 12/13/2018 | 12/13/2018 | A | PART |
Troy Cobbley
|
|
|
Only the four fire smoke dampers and the east side duct detector were tested today in the Gym. The west side hvac unit did not function.
Phone #: ###-#### Inspection requested via web by Ken Webster
|