INSP-Final Inspection | 1/15/2019 | 1/16/2019 | 1/16/2019 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
Roy Phone #: ###-####
|
INSP-Final Inspection | 1/2/2019 | 1/4/2019 | 1/4/2019 | A | FAIL |
Troy Cobbley
|
|
|
Permit can be finaled when the new backflow has been approved by plan review.
Jeff Phone #: ###-####
|
INSP-Final Inspection | 12/19/2018 | 12/21/2018 | 12/21/2018 | A | FAIL |
Jim Page
|
|
|
Flow switch did not activate with water flow.
Rough in and Final inspection. POC is Jeff Jeager Phone #: ###-#### Inspection requested via web by Brett Lawatch
|
INSP-Sprinkler Rough-in | 12/19/2018 | 12/21/2018 | 12/21/2018 | A | PASS |
Jim Page
|
|
|
Rough in inspection for overhead fire sprinkler piping complete.
Rough in and Final inspection. POC is Jeff Jeager Phone #: ###-#### Inspection requested via web by Brett Lawatch
|
INSP-Final Inspection | 12/7/2018 | 12/10/2018 | 12/10/2018 | A | CANC |
Troy Cobbley
|
|
|
Not ready for final yet.
As-Builts have been approved by Tim Frost. Insulation has bee fixed. Robert Mullins is Foreman on job. Phone #: ###-#### Inspection requested via web by Brett Lawatch
|
INSP-Sprinkler Rough-in | 12/7/2018 | 12/10/2018 | 12/10/2018 | A | PART |
Troy Cobbley
|
|
|
See the city approved plans for locations that need corrections that include insulation blocking heads in the attic, insulation needs to be provided in one location and removed in another at the east exterior exit, it appears per the data sheet that the COIN heads have been installed correctly. Areas in question have been marked on the plans.
As-Builts have been approved by Tim Frost. Insulation has bee fixed. Robert Mullins is Foreman on job. Phone #: ###-#### Inspection requested via web by Brett Lawatch
|
INSP-Sprinkler Rough-in | 11/19/2018 | 11/19/2018 | 11/19/2018 | A | PART |
Troy Cobbley
|
|
|
Need data sheets for the sprinkler heads to veriy their listed spacing/obstruction Phone #: ###-#### Inspection requirements. Need insulation removed from the BB1 heads in the attic. Need city approved plans for the changes/additions.
requested via web by Brett Lawatch
|
INSP-Sprinkler Rough-in/Hydro | 11/9/2018 | 11/13/2018 | 11/13/2018 | A | PART |
Troy Cobbley
|
|
|
Overhead Rough-In is partially passed. See the city approved plans for corrections needed with some earthquake bracing. Also need ceilings removed to inspect the new sprinkler piping. As-builts will be required prior to a final sign off showing the riser being relocated and some small pipe size changes and new area being sprinklered. The overhead hydro inspection passed with no visible loss on the guage.. Cesar Rodriguez is Foreman Phone #: ###-#### Inspection requested via web by Brett Lawatch
|
INSP-Sprinkler Rough-in/Hydro | 11/8/2018 | 11/9/2018 | 11/9/2018 | P | CANC |
Troy Cobbley
|
|
|
Overhead Rough-in and Hydro inspection. Cesar Rodriguez is the foreman. Phone #: ###-#### >> Inspection requested via web by Brett Lawatch Inspection cancelled from web by: Brett Lawatch
|
INSP-Supply line flush | 11/1/2018 | 11/2/2018 | 11/2/2018 | A | DONE |
Jim Page
|
|
|
Main line flush complete.
This is to flush and final the underground fire main, Cesar Rodriguez is the project foreman on site. UG was already rough-in/hydro tested on 10/10/18. Phone #: ###-#### Inspection requested via web by Brett Lawatch
|
INSP-Sprinkler Rough-in/Hydro | 10/9/2018 | 10/10/2018 | 10/10/2018 | A | PASS |
Troy Cobbley
|
|
|
underground hydro test passed - Robert Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 10/8/2018 | 10/9/2018 | 10/9/2018 | P | PART |
Troy Cobbley
|
|
|
Bury depth has been corrected. Underground supply piping can be covered. Not ready for hydro test yet.
Underground, 2hr hydro - Robert Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 10/4/2018 | 10/5/2018 | 10/5/2018 | P | FAIL |
Troy Cobbley
|
|
|
The underground supply line is not buried deep enough. It appears to need atleast 6" more just as it is getting to the corner of the building and may need more where the 90 is to turn into the building. No hydro test performed
underground // Robert Phone #: ###-####
|