Description |
[D&B Supply Stockroom]
The fire sprinkler scope of work consists of protecting a stock room with ESFR sprinklers. The system will be supplied by a new 750 Gpm @ 60 Psi fire pump. The system is designed as a small 6”x6”x3” grid.
Location on Plan - North
Commodity - Animal Food, Tools, Clothing, Machinery
Classification - Class I-IV
Storage Type (rack, solid pile, etc.) - Racks
Pallet Type (wood or plastic) - Wood
Aisle Width - 6’-10’
Height of Storage - 18’
Ceiling Height - 23’-6”
Encapsulated - No
Solid Shelves - No
Smoke and Heat Vents - No
Draft Curtain - No
In Rack Sprinklers - No
Sprinkler Type - ESFR
High Temperature Sprinklers Required - ESFR
Applicable NFPA Section - T 16.2.3.1
Hydraulic Design Criterion - K=25.2, 15#, 12 Sprinklers (4 on 3 lines)
Hose Stream Requirements - 250 Gpm