INSP-Final Inspection | 6/17/2019 | 6/18/2019 | 6/18/2019 | P | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, final fire sprinkler inspection complete.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Final Inspection | 6/14/2019 | 6/17/2019 | 6/17/2019 | A | FAIL |
Jim Page
|
|
|
Flow switch test complete, numerous fire sprinklers have gaps next the head when escutcheon is fitted, on-site foreman has notified GC but patches have not been completed. Gaps/painting around heads needs to be complete for final inspection.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 3/25/2019 | 3/26/2019 | 3/26/2019 | P | PASS |
Jim Page
|
|
|
Rough to cover/tenting inspection for overhead fire sprinkler piping complete, approved for cover.
Tenting at same time as rough/hydro. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in/Hydro | 3/25/2019 | 3/26/2019 | 3/26/2019 | P | PART |
Jim Page
|
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|