INSP-Final Inspection | 2/1/2019 | 2/5/2019 | 2/5/2019 | A | PASS |
Jim Page
|
|
|
Previously noted items have been corrected. Final hood supression system is complete.
3rd times the charm for the electrical trip test! Phone #: ###-#### Inspection requested via web by Don Kartchner
|
INSP-Final Inspection | 1/25/2019 | 1/29/2019 | 1/29/2019 | A | FAIL |
Jim Page
|
|
|
Appliance under hood did not de-energize when hood system activated, per code all energy sources need to be isolated under the hood during system activation.
Coordinated with Jim Page, to do inspection at 8 am! Thanks! -Zach w/ Firexpert. Phone #: ###-#### Inspection requested via web by Don Kartchner
|
INSP-Final Inspection | 1/24/2019 | 1/25/2019 | 1/25/2019 | A | CANC |
Jim Page
|
|
|
Called point of contact but there was no answer, inspection request will need to be rescheduled, this request is cancelled.
Re-inspection of the electrical trip test. Phone #: ###-#### Inspection requested via web by Don Kartchner
|
INSP-Final Inspection | 1/21/2019 | 1/23/2019 | 1/23/2019 | A | FAIL |
Jim Page
|
|
|
Power to little fryer on left did not isolate when suppression system was tripped, all energy needs to be isolated with hood activation. Hood has excessive build up of grease behind filoters, hood needs cleaned before next inspection.
I''m trying to do this final early in the morning, so they can still open up for regular business hours. Thank you! Phone #: ###-#### Inspection requested via web by Don Kartchner
|