INSP-Final Inspection | 5/10/2019 | 5/10/2019 | 5/10/2019 | A | PASS |
Mark Scharfen
|
|
|
Passed fire alarm testing. State Fire to send in as build showing trouble instead of supervisory on tampers as panel has no supervisory function.
Doug Phone #: ###-####
|
INSP-Final Inspection | 3/28/2019 | 3/29/2019 | 3/29/2019 | A | FAIL |
Jim Page
|
|
|
West side dry system tamper is labeled west anti-freeze, west anti-freeze tamper is not reporting to panel. FDC bell is not hooked up to alarm pressure switch on east and west dry systems.
alarm not sprinklers // Barnie Phone #: ###-####
|
INSP-Final Inspection | 3/26/2019 | 3/27/2019 | 3/27/2019 | A | NR |
Jim Page
|
|
|
Fire sprinklers were not ready for inspection, no restricted orifice provided.
Barnie Phone #: ###-####
|
INSP-Final Inspection | 3/21/2019 | 3/22/2019 | 3/22/2019 | P | PART |
Jim Page
|
|
|
Final fire alarm inspection for related items in Workout Anytime TI complete, remaining items on this permit that deals with shell dry system to be completed at a later date.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug
|
INSP-Final Inspection | 3/12/2019 | 3/12/2019 | 3/12/2019 | P | NR |
Jim Page
|
|
|
Dry systems are not ready to test, deficiencies on the fire sprinkler system needs to be corrected before fire alarm final.
Call prior to going Phone #: 2089546009 >> Inspection requested via mobile web by Kenny Leslie
|