INSP-Final Inspection | 12/11/2019 | 12/12/2019 | 12/11/2019 | A | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection is complete.
Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
INSP-Final Inspection | 12/11/2019 | 12/12/2019 | 12/11/2019 | P | CANC |
Jim Page
|
|
|
Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
|
INSP-Final Inspection | 12/9/2019 | 12/9/2019 | 12/9/2019 | P | CANC |
Troy Cobbley
|
|
|
Please all Jess before heading down. Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
|
INSP-Sprinkler Rough-in/Hydro | 7/8/2019 | 7/8/2019 | 7/8/2019 | P | PASS |
Jim Page
|
|
|
All tenting in place at time of inspection, rough to cover inspection for overhead fire sprinkler piping complete, approved for cover.
Please call James Mair ###-#### Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
INSP-Sprinkler Rough-in | 7/2/2019 | 7/5/2019 | 7/5/2019 | A | FAIL |
Troy Cobbley
|
|
|
I tried calling the contact phone number three times but it won't even ring. I tried calling Clarence but it just goes to voice mail. I went to job site and made no contact. I however walked and looked at the tenting. On the main level laundry room the cpvc piping disappears behind the insulation on the wall (not sure what is going on here) and the ladder has been removed so I have no access to the upper floor to look at tenting. I walked around the house but I'm unsure it the roofing is approved to walk on. No piping can be covered. Sticker left on site.
Please call James Mair ###-#### Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
INSP-Sprinkler Rough-in | 7/1/2019 | 7/1/2019 | 7/1/2019 | P | PART |
Troy Cobbley
|
|
|
The rough-in appears to match the revised plans. Piping can not be covered until a tenting inspection has been passed. Hanger issue was not resolved yet.
Clearance Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 6/25/2019 | 6/25/2019 | 6/25/2019 | P | FAIL |
Jim Page
|
|
|
Piping installed does match city approved drawings. Overspaced hangers on level 1. System held 200 psi for hydrostatic test but if changes need to be made to match city approved drawings then a re-hydro will be required. Head in level 3 bedroom is to close to heat register, need 24 inchs off of heat registers with 13D.
Plans are stuffed in riser drain valve Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|