Information based on query as of Saturday, May 4, 2024.
Permit Information
Permit NumberFIR19-00322
StatusFinaled
Name GUARDIAN ALARM SYSTEMS LLC
Site Address 503 S ASH ST
Project NameAsh St Townhomes East Bldg
Customer Number 
ePlanReviewYes
Description
THIS IS A NEW SPRINKLER MONITORING SYSTEM. THE PROJECT SCOPE INCLUDES A SMOKE DETECTOR ABOVE THE FACP, A MANUAL PULL STATION, AND ONE SENSORY UNIT WITH VISUAL/AUDIBLE NOTIFICATION.RETAIL/OFFICE AREA IS CONSIDERED A SHELL AND SEPARATED OCCUPANCY IN ACCORDANCE WITH 2015 IBC 508.4. THE CURRENT OCCUPANCY TYPES AND LOADS IN THESE AREAS DO NOT REQUIRE A FIRE ALARM SYSTEM AT THIS TIME.THE FIRE ALARM SYSTEM WILL NOT BE EXTENDED INTO THE RETAIL/OFFICE AREAS UNDER THIS PERMIT. THE DWELLING UNITS WILL HAVE THE CAPABILITY OF ADDING NOTIFICATION IN THE FUTURE.THERE IS ONE UNIT THAT WILL HAVE AUDIBLE/VISUAL NOTIFICATION. ALL CO DETECTORS AND 120V SINGLE/MULTI-STATION SMOKE ALARMS ARE BEING PROVIDED AND INSTALLED BY OTHERS AND ARE NOT PART OF THE FIRE ALARM SYSTEM.PER THE ARCHITECTURAL/MECHANICAL PLANS, THERE ARE NO AUTOMATIC LIFE SAFETY SHUTDOWN REQUIREMENTS FOR ANY HVAC AND/OR FIRE/SMOKE DAMPERS.
This work is associated with BLD17-04464.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/18/20196/19/20196/19/2019APASS
DetailsJim Page

Previously noted items have been corrected, final fire alarm inspection complete.

Phone #: ###-#### Inspection requested via web by Matt Casey
INSP-Final Inspection6/14/20196/17/20196/17/2019PFAIL
DetailsJim Page
Levels 1 and 2 flow switch labeleing was incorrect, level 1 was reporting as level 2 and level 2 was reporting as level 1.

Mark will handle inspection. Matt is on vacation Phone #: ###-#### Inspection requested via web by Matt Casey