INSP-Final Inspection | 12/26/2019 | 12/27/2019 | 12/27/2019 | A | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection for area of work complete.
Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|
INSP-Sprinkler Rough-in | 12/19/2019 | 12/20/2019 | 12/20/2019 | P | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, rough in inspection is complete, hardlids approved for cover.
Contact: Steve Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|
INSP-Sprinkler Rough-in | 12/10/2019 | 12/12/2019 | 12/12/2019 | A | FAIL |
Jim Page
|
|
|
Walls do not go all the way to deck, sprinkler system needs to comply with 8.15.23 of the 2016 NFPA 13.
Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|