Information based on query as of Sunday, June 16, 2024.
Permit Information
Permit NumberFIR19-00871
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 7344 N LUCY ROSE LN
Project NameEAGLEHAWK APTS UNDERGROUND #5
Customer Number 
ePlanReviewYes
Description
**QUICK PERMIT** Building #5 - Underground Only.. 2" DEDICATED FIRE LINE TO BE INSTALLED FROM CITY MAIN TO NEW APARTMENT BUILDING FOR A NEW NFPA 13R FIRE SPRINKLER SYSTEM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/18/20206/18/20206/18/2020PPASS
DetailsJim Page
Final inspection for underground supply complete.

Please call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Supply line flush5/29/20206/1/20206/1/2020ADONE
DetailsJim Page
Underground main line flush witnessed.

Scheduled for 9am with Stacy at Suez. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro5/27/20205/27/20205/27/2020PDONE
DetailsJim Page
Hydrostsic test for underground supply witnessed, no pressure loss observed at gauge before backflow.

Underground hydro. Ready any time, call James before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in11/25/201911/26/201911/26/2019APASS
DetailsJim Page
Previously noted items have been corrected, underground approved for cover.

Underground rough to cover. Please call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in11/25/201911/25/201911/25/2019AFAIL
DetailsJim Page
Bury depth of 54 inches to top of pipe not met. Attach bury wire to pipe, cover is not approved.

Call before heading out, underground rough to bury (hydro in warm weather or closer to final) Phone #: ###-#### Inspection requested via web by Anthony Minichiello