Information based on query as of Tuesday, April 30, 2024.
Permit Information
Permit NumberFIR20-00061
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 7353 N LUCY ROSE LN
Project NameEAGLE HAWK APTS. BLD 1
Customer Number 
ePlanReviewYes
Description
TFSS TO INSTALL A NEW NFPA 13R FIRE SPRINKLER SYSTEM IN THIS NEW APARTMENT BUILDING.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/23/20206/24/20206/24/2020APASS
DetailsJim Page
Final fire sprinkler inspection is complete.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in4/15/20204/15/20204/15/2020PPASS
DetailsJim Page
Tenting has been corrected, all tenting in place at time of inspection, cover is approved.
INSP-Sprinkler Rough-in/Hydro4/15/20204/15/20204/15/2020PDONE
DetailsJim Page
Hydrostatic test witnessed, no pressure loss observed at riser provided gauge.

Hydro and tenting, call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro4/13/20204/13/20204/13/2020PFAIL
DetailsJim Page
System lost 20psi during hydro. Tenting has been comprimised by other trades, cover is no longer autorized, a re-inspection for tenting is required. Cover sticker has been removed, any and all cover material installed before tenting re-inspection that prevents a visual inspection of the pipe will be required to be removed.
Hydro RE-inspection. Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro4/8/20204/9/20204/9/2020PCANC
DetailsJim Page
Cancelled per conversation with point of contact, will be rescheduled for a later date.

Hydrostatic test Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in3/25/20203/26/20203/26/2020APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping is complete. All tenting in place at time of inspection, cover is approved. Cover approval sticker has been placed.

Overhead rough/tenting, call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello